Plan Distance Between Components
Follow the table below for maximum distances between system components. Wire gauge must meet local codes and in some circumstances wire gauge requirements change based on distance. Refer to Appendix B for wire gauge requirements.
Distance to Measure | Maximum Cable Length |
---|---|
Backup Switch to Powerwall+* |
150 ft (45 m) for 16 AWG (1.5 mm2) wire |
Powerwall+ to Internet router (wired Ethernet connection) | 328 ft (100 m) |
*Total length of communications cable, including daisy-chained connections, through last Powerwall in chain
Note
As noted in
Required Supplies, minimum 600 V rated 4-conductor (twisted
pair optional) or double-insulated (with one twisted pair) shielded cable is required
for the communication connection between Powerwall and the Backup Switch; see Required Supplies for custom
cable requirements.
CAUTION
Failure to follow
minimum cable size and length requirements may result in intermittent or unreliable
operation of the Powerwall+ system. In systems that do not meet
these minimum requirements, performance issues may arise even after successful device
setup.