17/09/2024 06:44:20

Install Stacked Expansion Units

Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Stacked Expansion units must be ground mounted. Do not attempt to install stacked units above ground on a bracket, or in any configuration other than ground-mounted.
Informational PurposesAn informational icon, calling your attention
Note
Follow all Powerwall 3 guidance for choosing a location to install Expansion units, clearance requirements, and instructions to remove the units from packaging and transport them with the Powerwall dolly.
  1. Determine where the Expansion units and Powerwall 3 will be installed based on the number of units:
    Figure 1. Expanded View of (2) Stacked Expansion Units
    Informational PurposesAn informational icon, calling your attention
    Note
    When installing the wall bracket shims:
    • Do not install shims if the wall bracket is mounted directly to the wall
    • Install shims if the wall bracket is fastened to an Expansion unit
    1. Depending on how many units will be stacked, confirm the minimum footprint area is available in front of where the bracket will be installed:
      (2) Units (3) Units (4) Units
      14 x 24 ¼ in (356 x 610 mm) 20 x 24 ¼ in (508 x 610 mm) 27 x 24 ¼ in (686 x 610 mm)
    2. Using a level, confirm the ground slope within the required footprint area (in any direction) is less than or equal to 1 ¼ inches (32 mm). If the ground slope is greater than this value, the ground slope must be corrected or the stacked configuration must be mounted in another location.
    Ground Slopes Away From Wall Ground Slopes Toward Wall
  2. Determine the height at which the wall bracket will be mounted:
    1. Identify the highest point within the required footprint area; this will be the starting reference point for mounting the wall bracket. Determine the difference between this point and the base of the wall.
      Informational PurposesAn informational icon, calling your attention
      Note
      For a flat surface or a surface that slopes away from the wall, the base of the wall is the highest point.
      Informational PurposesAn informational icon, calling your attention
      Note
      As noted in the previous step, the difference between this point and the base of the wall must be less than or equal to 1 ¼ inches (32 mm).
    2. For a flat surface or a surface that slopes away from the wall, the wall bracket is mounted with the upper row of fastener slots 30 inches (760 mm) from the base of the wall (see Bracket Measurements Relative to Expansion Unit and Floor).
    3. For a surface that slopes toward the wall, add the difference in slope (determined in step 2a) to the baseline 30 inches (760 mm). For instance, if the difference between the highest point in the footprint area and the base of the wall is 1 inch (25 mm), mount the wall bracket with the upper row of fastener slots 31 inches (785 mm) from the base of the wall.
      Wall Bracket Height for Flat Surface or Ground Sloping Away from Wall Wall Bracket Height for Ground Sloping Toward Wall
      Warning IconA warning icon, calling your attention to a possibly risky situation
      Warning
      It is critical that the slope of the installation area is accurately measured and the wall bracket is installed at the correct height to ensure the units can be leveled and the stacked assembly shall retain its structural integrity.
      • If the wall bracket is mounted too low, the units will not properly engage with the wall bracket
      • If the wall bracket is mounted too high, the units will not be supported by their feet
  3. Safely shut the system down:
    1. If a System Shutdown Switch is present, push it to initiate Rapid Shutdown. If there is no System Shutdown Switch, turn the Enable switch on the Powerwall 3 to OFF.
    2. Open the Powerwall 3 AC circuit breaker.
    3. Wait 30 seconds before proceeding with any work.
      Warning IconA warning icon, calling your attention to a possibly risky situation
      Warning
      Risk of electric shock from stored energy. Wait 30 seconds after disconnecting all sources of supply before proceeding.
  4. To lift and transport the Expansion unit, follow all instructions in STEP 2: Remove Powerwall 3 from Packaging and Transport Using the Powerwall Dolly to use the Powerwall dolly, noting where the two lift handles are connected on the Expansion (X):
  5. Using a drill and level, mount the Expansion unit bracket to the selected wall. See Powerwall 3 Wall Bracket Anchoring Details for Wall-mounting or Ground-mounting on Approved Foundation for additional details on the type and number of fasteners to use.
    Figure 2. Bracket Measurements Relative to Expansion Unit and Floor
    Informational PurposesAn informational icon, calling your attention
    Note
    These bracket measurements are the same for both Expansion and Powerwall 3 units.
    Warning IconA warning icon, calling your attention to a possibly risky situation
    Warning
    Only install fasteners in the (4) slots on the horizontal bracket segments. Do not install fasteners on the vertical (center) segment, as these are not structural mounting holes.
    Informational PurposesAn informational icon, calling your attention
    Note
    The mounting bracket shims included in the Expansion stacking kit are not used for the unit mounted directly to the wall. The shims are only required to secure the bracket when it is being mounted to the front of an Expansion unit.
  6. Confirm the leveling feet are screwed all the way in to the Expansion unit. This is required to ensure the unit can be adjusted once the remaining units in the stack have been installed.
  7. Move the dolly toward the wall, positioning the Expansion unit so that the mounting cleats are just above the flanges on the bracket.
  8. Lower the Expansion unit until both the upper and lower sets of cleats engage the flanges on the bracket.
    Warning IconA warning icon, calling your attention to a possibly risky situation
    CAUTION
    Confirm the unit is fully seated on all four cleats before proceeding.
    Informational PurposesAn informational icon, calling your attention
    Note
    The mounting bracket shims included in the Expansion stacking kit are not used for the unit mounted directly to the wall. The shims are only required to secure the bracket when it is being mounted to the front of an Expansion unit.
  9. To install the fan front cover in the open space at the top of the enclosure, first align the bottom of the cover with the enclosure and push it into place. With the bottom of the cover secured, push in the top of the cover, ensuring it snaps into place.
  10. Install the (6X) fir tree plugs in the fastener holes on the top and sides of the enclosure.
  11. Use an 11/16 inch (or 17 mm) wrench to adjust the leveling feet until the unit is level. The unit should be within +/- 2 degrees in any direction.
    Informational PurposesAn informational icon, calling your attention
    Note
    The top of each foot must be visible above the threaded boss; do not unscrew the foot so far that the top is no longer visible.
  12. Mount another Expansion unit to the front of the installed Expansion unit enclosure:
    1. Using the (4X) provided Torx T40 fasteners, mount the next Expansion unit bracket to the front of the installed Expansion unit enclosure. Torque the fasteners to 26 Nm (230 in-lb).
    2. Install the (4X) bracket shims to secure the bracket against the Expansion enclosure.
      Informational PurposesAn informational icon, calling your attention
      Note
      Ensure each shim is aligned with the edge of the bracket and is fully seated.
    3. With the next Expansion unit on the dolly, move the dolly toward the wall, positioning the unit so that the mounting cleats are just above the flanges on the bracket.
    4. Lower the Expansion unit until both the upper and lower sets of cleats engage the flanges on the bracket.
    5. Install the fan front cover and the (6) fir tree plugs in the fastener holes as described in steps 9 and 10.
    6. Use an 11/16 inch (or 17 mm) wrench to adjust the leveling feet until the unit is level. The unit should be within +/- 2 degrees in any direction. When confirming the units are level with each other, place the level on either side of the unit and balance the level on the front edge of each unit.
      Informational PurposesAn informational icon, calling your attention
      Note
      The top of each foot must be visible above the threaded boss; do not unscrew the foot so far that the top is no longer visible.
  13. Repeat step 12 for a third Expansion if present.
  14. Once all Expansion units have been installed, repeat step 12 to mount the Powerwall 3 to the front of the stack.
  15. Begin with STEP 6: Make Solar PV Connections to complete all Powerwall 3 wiring, finishing by installing the front cover.
    Informational PurposesAn informational icon, calling your attention
    Note
    Powerwall 3 must always be installed at the front of an Expansion unit stack. If the Powerwall 3 was previously installed, it must be uninstalled so that it can be moved to the front of the new stack.
    Informational PurposesAn informational icon, calling your attention
    Note
    Alternatively, another Expansion with the Wall-Mount kit (Tesla P/N 1978069-00-A) can be mounted to the front of the stack.
  16. Connect the Expansion unit to the Powerwall 3 (or to another Expansion unit):
    1. Using a Torx T40 bit, loosen the fastener holding the Expansion port cover.
      Warning IconA warning icon, calling your attention to a possibly risky situation
      Warning
      STOP. Before opening Expansion port covers:
      • Do not open the Expansion Port cover if Expansion / Powerwall 3 is directly exposed to any of the following conditions:
        • Rain
        • Snow
        • High winds (>30 mph)
      • Do not leave the Expansion Port open for extended periods or in high debris/dust conditions
      Doing so may allow water and/or debris to contact the sensitive internal components of Powerwall 3 / Expansion. This may lead to product damage and could potentially void the product warranty.
    2. Insert a cabinet tip screwdriver in the small slots at the top and bottom of the port cover to pry it loose. Remove the cover.
      Informational PurposesAn informational icon, calling your attention
      Note
      Keep the Expansion port cover in case the Expansion port needs to be covered again for any reason. Store the cover in the protective packaging from the harness to keep it clean.
      Informational PurposesAn informational icon, calling your attention
      Note
      If replacing the Expansion port cover, torque the port cover screw to 100 in-lb (11 Nm).
    3. Visually inspect the Expansion port and confirm there is no debris in the port.
    4. Remove the protective packaging from the end of the Expansion Harness being plugged in.
      Informational PurposesAn informational icon, calling your attention
      Note
      The Expansion harness with Tesla P/N 1875157-05-x must be used when connecting Expansion units in a stacked configuration.
    5. Visually inspect the Expansion Harness connector and confirm there is no dirt or debris on the connector. If there is dirt / debris on the connector:
      • Clean the dirt / debris from the connector
      • If it is not possible to adequately clean the connector, use a new Expansion Harness
    6. Plug one end of the Expansion Harness into the Expansion unit. Torque the T40 harness screw on the connector to 100 in-lb (11 Nm).
    7. Route the Expansion Harness to the Powerwall 3 (or other Expansion unit).
    8. Remove the Expansion port cover from the Powerwall 3 (or other Expansion unit) and plug the Expansion Harness in. Torque the T40 harness screw on the connector to 100 in-lb (11 Nm).
    9. Ensure each end of the Expansion Harness is fully seated in its port; it will be possible to confirm the harness is fully seated when there is no gasket exposed.