Required Equipment

One of the following two kits is required:

Neurio Meter

  • Energy meter kit: Tesla P/N 1938241-00-A
    1Energy meter
    2Current Transformers (CTs)
    3Voltage line harness
    4RS-485 communication harness
    Informational PurposesAn informational icon, calling your attention
    Note
    The energy meter must be procured from Tesla as it ships with firmware required for this application.
  • Wago 2-position and 3-position lever nuts for splicing communication harness and energy meter voltage harness where required
  • Wire nut capping the blue voltage harness wire

Tesla Remote Meter

  • Tesla P/N North America 2045796-00-x
Part Description Quantity
1 Tesla Remote Meter 1
2 Tesla 200 A CT (1.5 m (59 in)) 2
3 Voltage harness (600 mm (23.6 in)) 1
4 External antenna 1
5 Antenna extension 1
6 Fasteners 2
7 RS485 Harness (P/N 2045794-xx-y) 1
Informational PurposesAn informational icon, calling your attention
Note
Neurio CTs are not compatible with Tesla Remote Meter.
Install type Requirements
Single-phase with one line conductor 1 CT
Single-phase with two line conductors 2 CT
Three-phase 3 CT
Informational PurposesAn informational icon, calling your attention
Note
If you require more CTs than provided in your region's kit for installation, individual CTs may be purchased (P/N 2033376-xx-y). 3.5m extensions for CTs may also be purchased (P/N 2060713-x-y)

Tesla Remote Meter Accessories

Informational PurposesAn informational icon, calling your attention
Note
These accessories are not included in the Tesla Remote Meter kit. They must be ordered individually wherever required.
Part Description Tesla P/N Quantity
Tesla 200 A CT (1.5 m (59 in)) 2033376-xx-y 2
CT extension (3.5 m (138 in)) 2060713-xx-y 1
Informational PurposesAn informational icon, calling your attention
Note
The Wi-Fi antenna included in the energy meter kit are not used.

  • Use 16 AWG shielded twisted pair cable to extend RS485 harness as needed.
    Informational PurposesAn informational icon, calling your attention
    Note
    The 600V-rated cable must be used if this wiring is to be run through the same conduit as the power circuits (if not, 300V-rated cable is sufficient).