Required Tools and Supplies
Accessory Bag (Tesla P/N 1857363-00-x)
- (6) M6 fasteners for front cover (Tesla P/N 1847553-00-A)
- (6) MPPT jumpers
- (2) cable tie mounts with (2) cable ties for grouping conductors
- (1) small clamp-on ferrite core for low voltage harness
- Powerwall 3 P/N 1707000-00-H and lower: (2) large clamp-on ferrite cores with (2) cable ties for the AC and PV conductors
- Powerwall 3 P/N 1707000-00-J and higher: (1) metal PV shield
Required Tools
- Powerwall dolly (Tesla P/N 1856187-xx-y)
- MC cable cutter (Tesla P/N 1879720-xx-y)
- Required when using PVC-MC cable
- ¾" (19 mm) drill socket
- Up to 3/32” (3 mm) electronics tip screwdriver
- Up to 3/16” (4.5 mm) electronics tip screwdriver
- Torx T20 bit
Required Supplies
- (1X) if floor-mounting using single fastener
- (4X) if using wall bracket
- Metal conduit only
- Pre-made Ethernet cables
- Minimum NEMA 4 (IPX5) conduit
hubsNoteMinimum NEMA 4 (IPX5) fittings are required when installing outdoors. When Powerwall 3 is installed indoors and there is no risk of water ingress, indoor-rated fittings can be used.
Approved Conduit | Minimum NEMA 4 (IPX5) Fittings |
---|---|
PVC-MC Cable | ¾” PVC-MC Connector |
1” PVC-MC Connector | |
EMT | ¾” Bridgeport 251-RT2 Connector |
1” Bridgeport 252-RTI2 Connector | |
RMC | ¾” RMC Myers Hub with RMC conduit |
1” RMC Myers Hub with RMC conduit | |
¾” RMC Sealing Locknut with RMC conduit | |
1” RMC Sealing Locknut with RMC conduit | |
1-¼” RMC Sealing Locknut with RMC conduit |