Make Powerwall 3 Wiring Connections

Make Powerwall 3 PV Power Connections

Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Turn the Powerwall 3 Enable switch OFF before doing any wiring.
1

MPPT Positive PV inputs: 10-6 AWG (6-16 mm2)
Up to 4.5 mm or 3/16 inch cabinet / electronics tip screwdriver

2

MPPT Negative PV inputs: 10-6 AWG (6-16 mm2)
Up to 4.5 mm or 3/16 inch cabinet / electronics tip screwdriver

3

Ground terminals: 12-4 AWG (2.5-25 mm2)
Torque to 35 in-lb with Torx T20

4 Gather conductors in provided cable tie
5 Leave a service loop
Important Notes on Installing MPPT Jumpers:
  • Jumpers can be used when IMP > 13A. Use jumpers to allow a single MPPT to intake strings with a total IMP up to 26A
  • Land the combined circuit (2 strings in parallel = 1 circuit) or string with IMP greater than 13A in the terminal and connect the jumper from:
    • MPPT 1 to MPPT 2
    • MPPT 5 to MPPT 6
  • MPPT PV inputs 3 and 4 cannot be combined and are closed from the factory
  • Only use the Powerwall 3 MPPT jumpers (Tesla P/N 1784893-xx-y) provided in the Powerwall 3 accessory bag
    Figure 1. Powerwall 3 MPPT Jumper
  • Do not use jumpers on Solar Roof jobs - you cannot parallel more than two strings so combined circuit IMP will always be less than 13A DC
  • Ensure each jumper is fully seated in the connector!
Figure 2. Example PV Wiring Configuration: Up to (6X) Independent Strings where IMP of Each String < 13A
Figure 3. Example PV Wiring Configuration: Up to (6X) Pairs of Combined Strings where IMP of Each Combined Circuit < 13A
Informational PurposesAn informational icon, calling your attention
Note
This configuration is most common when installing Solar Roof with Powerwall 3.
Figure 4. Example PV Wiring Configuration: Up to (6X) Pairs of Combined Strings where IMP of Each Combined Circuit > 13A (Jumpers Required)

Connect Powerwall 3 to the Backup Switch / Backup Gateway 2 / Gateway 3

1

CN- (CAN LO): 24-16 AWG (0.2-1.5 mm2)
Up to 3 mm or 3/32 inch cabinet / electronics tip screwdriver

2

CN+ (CAN HI): 24-16 AWG (0.2-1.5 mm2)
Up to 3 mm or 3/32 inch cabinet / electronics tip screwdriver

3

GND: 24-16 AWG (0.2-1.5 mm2)*
Up to 3 mm or 3/32 inch cabinet / electronics tip screwdriver

4

12V+: 24-16 AWG (0.2-1.5 mm2)*
Up to 3 mm or 3/32 inch cabinet / electronics tip screwdriver

5 Strip back the cable jacket so that the wires lay flat, leaving room to install the front cover. Route the cable through the lower left tab
6 Leave a service loop

*18 AWG is the recommended minimum wire gauge due to potential voltage drop on long wire runs.

Informational PurposesAn informational icon, calling your attention
Note
CN- and CN+ must be twisted pair.
Informational PurposesAn informational icon, calling your attention
Note
The wire order for Backup Switch / Backup Gateway 2/ Gateway 3 is not the same as the wire order for Powerwall 3.

Make Powerwall 3 AC Power Connections

Connect Powerwall 3 to a 60A breaker.

1

N / L2 / L1: 10-4 AWG (6-25 mm2)
Up to 4.5 mm or 3/16 inch cabinet / electronics tip screwdriver

2

Ground terminals: 12-4 AWG (2.5-25 mm2)
Torque to 35 in-lb with Torx T20

3 Gather conductors in provided cable tie
4 Leave a service loop
Warning IconA warning icon, calling your attention to a possibly risky situation
CAUTION
If using a 60 A fuse as the Powerwall 3 overcurrent protection device, it must be a Class RK1 Fast Acting fuse. Use one of the following fuses or equivalent:
Fuse TypeManufacturerPart Number
Fast-Acting Fuse, Class RK1, >= 250VAC, CLFLittelfuseKLNR60
Eaton / BussmannKTN-R-60
Mersen / Ferraz ShawmutA2K60R

Install System Shutdown Switch Where Required

Warning IconA warning icon, calling your attention to a possibly risky situation
CAUTION
The System Shutdown Switch must be connected to Powerwall 3. Do not connect it to the Backup Gateway 2 as it will not work.
1

Rapid Shutdown IN: 24-16 AWG (0.2-1.5 mm2)
Up to 3 mm or 3/32 inch cabinet / electronics tip screwdriver

2

Rapid Shutdown OUT: 24-16 AWG (0.2-1.5 mm2)
Up to 3 mm or 3/32 inch cabinet / electronics tip screwdriver

3 Remove RSD jumper when installing System Shutdown Switch; otherwise, leave installed
4 Strip back the cable jacket so that the wires lay flat, leaving room to install the front cover. Route the cable through the lower left tab
5 Leave a service loop
6 Connect the RSD wiring to a suitable DC switch (see the Powerwall 3 with Backup Gateway 2, Backup Switch, or Gateway 3 installation manual for full details)
Informational PurposesAn informational icon, calling your attention
Note
See Multi-Powerwall 3 Installations for instructions to connect multiple Powerwall 3 units to a System Shutdown Switch.

Install Ferrite Cores / Metal PV Shield

For Powerwall 3 P/N 1707000-00-J and higher, install the metal PV shield and LV ferrite core:

1 Low voltage harness ferrite
2 Metal PV shield
Informational PurposesAn informational icon, calling your attention
Note
Ensure the PV shield is firmly in place and its edges do not protrude past the edges of the Powerwall 3 enclosure.
Informational PurposesAn informational icon, calling your attention
Note
When the metal PV shield is installed, additional ferrite cores are not required on the AC and PV wires.

For Powerwall 3 P/N 1707000-00-H and lower, install the (3X) ferrite cores:

1 AC ferrite
2 PV ferrite
3 Low voltage harness ferrite

Secure each ferrite with its provided cable tie.

Informational PurposesAn informational icon, calling your attention
Note
Ground wires do not need to be included in the ferrite cores.

Important Notes on Wire Routing

Figure 5. Good Wiring Example: AC Wiring Routed from Left, PV Wiring Routed from Right
1
  • AC is routed from left with service loop
  • AC wires are secured with a cable tie
2
  • PV is routed from right with service loop
  • PV wires are secured with a cable tie
3
  • Communication wire is routed from right, crossing the enclosure in the dedicated wiring space
  • Communication wire has a service loop
  • Communication wire is routed through left-side tab with cable jacket stripped back
Figure 6. Good Wiring Example: AC Wiring Routed from Right, PV Wiring Routed from Left
1
  • AC is routed from right, crossing the enclosure in the dedicated wiring space
  • AC wiring has a service loop
  • AC wires are secured with a cable tie
2
  • PV is routed from left, crossing the enclosure in the dedicated wiring space
  • PV wiring has a service loop
  • PV wires are secured with a cable tie
3
  • Communication wire is routed from right, crossing the enclosure in the dedicated wiring space
  • Communication wire has a service loop
  • Communication wire is routed through left-side tab with cable jacket stripped back
Figure 7. Bad Wiring Example: AC and Communication Wiring Blocking Front Cover
1 AC wires are routed across the front of the enclosure which would prevent the front cover from being installed
2
  • Communication wire is not routed through left-side tab
  • Communication cable jacket has not been stripped back
This wire will also prevent the front cover from being installed
Figure 8. Bad Wiring Example: Communication Wiring Blocking Wi-Fi Antenna
1
  • Communication wire is routed through right-side tab
  • Communication cable jacket has not been stripped back
When the communication wire is routed from the right, it blocks the Wi-Fi antenna. Not stripping back the cable jacked will prevent the front cover from being installed
Figure 9. Bad Wiring Example: Communication Wiring Blocking Front Cover, AC and PV Wiring Missing Service Loops and Cable Ties
1 AC and PV wiring do not have service loops
2 Communication cable is routed from top; no drip loop creates the potential for water to follow the cable and drip into the wiring terminals
3 AC and PV wires are not secured with cable ties