Make Powerwall 3 Wiring Connections
Make Powerwall 3 AC Power Connections
Connect Powerwall 3 to the appropriate breaker size
depending on the desired power / current output (configured in Tesla One):
Maximum Continuous Current | Power Output (AC) | Breaker (Overcurrent Protection) |
---|---|---|
48 A On-grid | 11.5 kW On-grid | 80 A* |
48 A | 11.5 kW (default) | 60 A |
41.7 A | 10 kW | 60 A |
31.7 A | 7.6 kW | 40 A |
24 A | 5.8 kW | 30 A |
*Powerwall 3 can only provide 15.4 kW when off-grid and when there is sufficient solar; when the system is on-grid, and/or when solar production is insufficient, Powerwall 3 will provide 11.5 kW. If enabling this feature, Powerwall 3 must be installed with an 80 A breaker and appropriately sized conductors.
1 | Ground terminals: 12-4 AWG (4-25 mm2), torque to 35 in-lb with Torx T20 |
2 | N / L2 / L1: 10-4 AWG (6-25 mm2), use up to 4.5 mm (3/16 inch) cabinet / electronics tip screwdriver |
3 | Gather conductors in provided cable tie |
4 | Leave a service loop |
CAUTION
If using a fuse
as the Powerwall 3 overcurrent protection
device, it must be a Class RK1 Fast Acting fuse. Use one of the following fuses
or equivalent:
Fuse Type | Manufacturer | Part Number |
---|---|---|
80 A Fast-Acting Fuse, Class RK1, >= 250VAC, CLF | Littelfuse | KLNR080 |
Eaton / Bussmann | KTN-R-80 | |
Mersen / Ferraz Shawmut | A2K80R | |
60 A Fast-Acting Fuse, Class RK1, >= 250VAC, CLF | Littelfuse | KLNR60 |
Eaton / Bussmann | KTN-R-60 | |
Mersen / Ferraz Shawmut | A2K60R | |
40 A Fast-Acting Fuse, Class RK1, >= 250VAC, CLF | Littelfuse | KLNR40 |
Eaton / Bussmann | KTN-R-40 | |
Mersen / Ferraz Shawmut | A2K40R | |
30 A Fast-Acting Fuse, Class RK1, >= 250VAC, CLF | Littelfuse | KLNR30 |
Eaton / Bussmann | KTN-R-30 | |
Mersen / Ferraz Shawmut | A2K350 |
Make Powerwall 3 PV Power Connections
Warning
Turn the Powerwall 3 Enable switch OFF before doing any wiring.
1 | Ground terminals: 12-4 AWG (4-25 mm2), torque to 35 in-lb with Torx T20 | |
2 | MPPT Positive PV inputs: 10-6 AWG (6-16 mm2) | Use up to 4.5 mm (3/16 inch) cabinet / electronics tip screwdriver |
3 | MPPT Negative PV inputs: 10-6 AWG (6-16 mm2) | |
4 | Gather conductors in provided cable tie | |
5 | Leave a service loop |
Important Notes on Installing MPPT
Jumpers:
- The jumpers provided in the Powerwall 3 accessory bag can only
be used with the Powerwall 3 model they shipped with:
Powerwall 3 Part Numbers Jumper Part Number Jumper Image 1707000-11-L or 170700-21-L 2009322-xx-y All other Powerwall 3 part numbers 1784893-xx-y CAUTIONThese jumpers are not interchangeable. Only install the jumpers that ship with the unit. - Jumpers can be used when IMP > 13A. Use jumpers to allow a single MPPT to intake strings with a total IMP up to 26A
- Land the combined circuit (2
strings in parallel = 1 circuit) or string with IMP greater than 13A
in the terminal and connect the jumper from:
- MPPT 1 to MPPT 2
- MPPT 5 to MPPT 6
- MPPT PV inputs 3 and 4 cannot be combined and are closed from the factory
- Do not use jumpers on Solar Roof jobs - you cannot parallel more than two strings so combined circuit IMP will always be less than 13A DC
- Ensure each jumper is fully seated in the connector!
Connect Powerwall 3 to the Backup Switch / Backup Gateway 2 / Gateway 3
1 | CN- (CAN LO): 24-16 AWG (0.2-1.5 mm2) | Use up to 3 mm (3/32 inch) cabinet / electronics tip screwdriver |
CN+ (CAN HI): 24-16 AWG (0.2-1.5 mm2) | ||
2 | GND: 24-16 AWG (0.2-1.5 mm2)* | |
12V+: 24-16 AWG (0.2-1.5 mm2)* | ||
3 | Leave a service loop |
*18 AWG is the recommended minimum wire gauge due to potential voltage drop on long wire runs.
Note
CN- and CN+ must be twisted pair.
Note
The wire order for Backup Switch /
Backup Gateway 2/ Gateway 3 is not the same as the wire order for Powerwall 3.
Install System Shutdown Switch Where Required
CAUTION
The System Shutdown
Switch must be connected to Powerwall 3. Do not connect it to the
Backup Gateway 2 as it will not work.
1 | Rapid Shutdown IN: 24-16 AWG (0.2-1.5 mm2) | Use up to 3 mm (3/32 inch) cabinet / electronics tip screwdriver |
2 | Rapid Shutdown OUT: 24-16 AWG (0.2-1.5 mm2) | |
3 | Remove RSD jumper when installing System Shutdown Switch; otherwise, leave installed | |
4 | Leave a service loop | |
5 | Connect the RSD wiring to a suitable DC switch (see the Powerwall 3 with Backup Gateway 2, Backup Switch, or Gateway 3 installation manual for full details) |
Note
See Multi-Powerwall 3 Installations for
instructions to connect multiple Powerwall 3 units to a System Shutdown Switch.
Install Ferrite Cores
- (1) large clamp-on ferrite core for the AC conductors
- (1) small clamp-on ferrite core for the TACO low voltage harness
CAUTION
Ferrite cores
are fragile; handle with caution.
Note
Ground wires do not need to be
included in the ferrite cores.
Important Notes on Wire Routing
1 |
|
2 |
|
1 |
|
2 |
|