Multi-Powerwall 3 Installations

Powerwall 3 can be installed with additional Powerwall 3 units for additional solar and storage capabilities, and/or with Powerwall 3Expansion units for additional storage (kWh).

Informational PurposesAn informational icon, calling your attention
Note
See the Powerwall 3 Installation Manual (with Backup Gateway 2, Backup Switch, or Gateway 3) for instructions to install Powerwall 3 with Expansion unit(s), including structural requirements for stacked configurations and Expansion Harness selection for wall-mounted configurations.
Maximum Number of Powerwall 3 Units Up to (4)Powerwall 3 units
Leader Powerwall 3 The Powerwall 3 connected to the via 12V / CAN communication wiring is designated as the Leader Powerwall 3
Informational PurposesAn informational icon, calling your attention
Note
The system is commissioned by connecting to the Leader Powerwall 3.
Follower Powerwall 3 Any Powerwall 3 other than the Leader is connected via inter-Powerwall Ethernet wiring and is designated as a Follower unit
Maximum Number of Expansion Units Up to (3) Expansion units (for a maximum total of (7) units)
Informational PurposesAn informational icon, calling your attention
Note
Expansion units must be connected to the Leader Powerwall 3; they will not function if connected to a Follower unit.
Powerwall 3 Compatibility with Expansion Units Powerwall 3 units with Tesla P/N 1707000-xx-J or greater are compatible with Expansions
Figure 1. Up to Four Powerwall 3 Units with up to Three Expansion Units, Installed with Backup Switch
Figure 2. Up to Four Powerwall 3 Units with up to Three Expansion Units, Installed with Backup Gateway 2
Figure 3. Up to Four Powerwall 3 Units with up to Three Expansion Units, Installed with Gateway 3

System Shutdown Switch with Multiple Powerwall 3 Units

Where a System Shutdown Switch is required, connect eachPowerwall 3 to a dedicated electrical contact of the switch. Ensure the installed System Shutdown Switch has enough electrical contacts for the number of units installed.

Figure 4. Good Wiring Example: Each Unit Connected to Electrical Contact in E-Stop
Figure 5. Bad Wiring Example: Both Powerwall 3 Connected to a Single Electrical Contact
Figure 6. Bad Wiring Example: Powerwall 3 Units Connected to E-Stop in Series (Does Not Work)
Figure 7. Bad Wiring Example: Second Powerwall 3 Not Connected to E-Stop

Connecting Powerwall 3 Units via Ethernet

All Powerwall 3 units must be connected via Ethernet. The units can be connected in any order, so long as each unit is connected to at least one other unit.

Figure 8. Option 1: Leader Powerwall 3 Connected to Customer Router via Wi-Fi (Leader at Start of Chain)
Figure 9. Option 2: Leader Powerwall 3 Connected to Customer Router via Wi-Fi (Leader in Middle of Chain)
Figure 10. Option 3: Leader Powerwall 3 Connected to Customer Router via Ethernet
Informational PurposesAn informational icon, calling your attention
Note
If connecting the system to the customer router via Ethernet, connect the router to either the first or last Powerwall 3 in the chain. Do NOT connect the router in the middle of the chain.

Commissioning Multi-Powerwall 3 Systems

For instructions to commission a multi-Powerwall 3 system, as well as for troubleshooting steps for common issues, see the Powerwall 3 Device Setup Guide.