Optional: Configure Powerwall 3 Maximum Power / Current Output
The default maximum power / current output for Powerwall 3 is 11.04 kW / 48 A . Beginning with software version 24.20, the power / current output can be configured to one of the following limits during device setup, except where it is limited by the local grid code requirements:
Nominal AC Output Power at 230 V (kW)4 | 3.68 | 5 | 6 | 7 | 8 | 9 | 10 | 11.04 |
Maximum Apparent Power (kVA) | 3.68 | 5 | 6 | 7 | 8 | 9 | 10 | 11.04 |
Maximum Continuous Current (A) | 16 | 21.7 | 26.1 | 30.4 | 34.8 | 39.1 | 43.5 | 48 |
Overcurrent Protection Device (A) | 20 | 32 | 32 | 40 | 50 | 50 | 63 | 63 |
This feature can be used for the following purposes:
- Compliance with utility-imposed requirements on maximum inverter power (for instance transformer capacity limits or interconnection requirements)
- Qualification for subsidies or economic benefits
- Replacing a Powerwall 2 or third party solar inverter with a Powerwall 3
Configuring a Power / Current Output
Note
When installing Powerwall 3, select the appropriate Powerwall 3 breaker size depending on the
desired power output (see the table above).
- If the system is running, select
Stop
System.
- Select
- Select the desired maximum current / power output from the dropdown menu.
- Select NoteOnce the setting has been confirmed, it cannot be changed by the installer. Contact Tesla Support if the setting must be changed.
.
- Document the configured maximum
current output on the Powerwall 3 product label (use a paint
pen to mark the configured value).