Backup Gateway 2 Specifications

Backup Gateway 2 Electrical Specifications

AC Voltage (Nominal)1 230 V (Line-to-Neutral)
400 V (Line-to-Line)
Feed-In Type Single Phase, Three Phase
Grid Frequency 50-60 Hz
Maximum Overcurrent Protection Device 100 A (single-phase service)
80 A (2- and 3-phase service)
Maximum Input Short Circuit Current2 16 kA
Overvoltage Category Category III
AC Meter Accuracy (+/– 0.2 %)
Compatible Earthing Systems3 TN or TT networks
Distribution boards intended to be operated by ordinary persons (DBO) Type Type B
1230 V (Line-to-Line) is not a supported three-phase configuration.
216 kA rating when installed with current limiting fuse compliant to BS 88.3; 10 kA rating without fuse.
3TT earthing networks supported for Gateways with part number 1152100-13-H and higher.

Environmental Specifications

Operating Temperature4 –20°C to 50°C
Operating Humidity (RH) Up to 100%, condensing
Maximum Altitude 3000 m
Ingress Rating IP55
Environmental Category Outdoor rated
Wet Location Rating Yes
Pollution Degree PD2
4 Performance may be de-rated in extreme ambient temperatures

Mechanical Specifications

Dimensions 584 x 380 x 127 mm
Weight 11.4 kg
Breaker space (DIN rail) Up to nine (9) single pole breakers
Mounting Options Wall mount

Compliance Information

Safety IEC 62109-1, IEC 62053-22, IEC 61439-1, IEC 61439-3
Environmental

RoHS Directive 2011/65/EU,

WEEE Directive 2012/19/EU,

Battery Directive 2006/66/EC

REACH Regulation EC 1907/2006