Powerwall 3 Specifications

System Technical Specifications

Model Number 1707000-xx-y
Nominal Grid Voltage (Input & Output) 230 VCA
Grid Type Single phase
Frequency 50 Hz
Protection Class Class I
Overvoltage Category III
Surge Withstand Voltage on AC Ports 4 kV
Surge Withstand Voltage on Communication Ports 2 kV
Radiated RF Immunity 35 V/m
Solar to Battery to Grid Round Trip Efficiency 89%1,2
Solar to Grid Efficiency 97.5%
Supported Islanding Devices Backup Gateway 2
Connectivity Wi-Fi (2.4 and 5 GHz), Dual-port switched Ethernet, Cellular (LTE/4G3)
Hardware Interface Dry contact relay 60V 2A, Rapid Shutdown (RSD) certified switch and 2-pin connector, RS-485 for meters
AC Metering Accuracy +/- 0.5%
Protections Integrated arc fault circuit interrupter (AFCI), Isolation Monitor Interrupter (IMI), Integrated DC Isolator
Customer Interface Tesla Mobile App
Warranty 10 years
Informational PurposesAn informational icon, calling your attention
Note
The model numbers in this manual call out "-XX-Y" for the suffix of the equipment model number. The wild cards are defined as follows:
  • "X" is a number and the one number in the model number representing a style code; form, fit, and function are not changed, and these numbers have no bearing on compliance.
  • "Y" is a letter, and the one letter in the model number representing a pedigree; form, fit, and function are not changed, and this letter has no bearing on compliance.

Solar Technical Specifications

Maximum Solar STC Input 20 kW
Withstand Voltage 600 V DC
PV DC Input Voltage Range 60 — 550 V DC
PV DC MPPT Voltage Range 60 — 480 V DC
MPPTs 3
Maximum Current per MPPT (IMP) 26 A
Maximum Short Circuit Current per MPPT (ISC) 30 A

Battery Technical Specifications

Nominal AC Output Power at 230 V (kW)4 3.68 5 6 7 8 9 10 11.04
Maximum Apparent Power (kVA) 3.68 5 6 7 8 9 10 11.04
Maximum Continuous Current (A) 16 21.7 26.1 30.4 34.8 39.1 43.5 48
Overcurrent Protection Device (A) 20 32 32 40 50 50 63 63
Nominal Battery Energy2 13.5 kWh
Maximum Continuous Charge Power (Powerwall 3 only) AC 5 kW
DC 5 kW
Maximum Continuous Charge Power (Powerwall 3 with up to (3) Expansions) AC Configurable up to 8 kW
DC 8 kW
Output Power Factor Rating 0 - 1 (Grid Code configurable)
Maximum Output Fault Current (1 s) 160 A
Maximum Short-Circuit Current Rating 10 kA
Load Start Capability (1 s) 185 A LRA (Locked Rotor Amps)
Power Scalability Up to 4 Powerwall 3 units supported
Energy Scalability Up to 3 Expansion units supported (for a maximum total of 7 units)

1Typical use case with energy produced by PV and stored in battery and then released to loads or the grid.

2Values provided for 25°C, at beginning of life. 3.3 kW charge/discharge power.

3Cellular connectivity subject to network service coverage and signal strength.

4Powerwall 3 can output up to 15.4 kW AC power at 64 A and 240 V.

Mechanical Specifications

Dimensions 1105 x 609 x 193 mm
Weight 130 kg
Mounting Options Floor or wall mount

Environmental Specifications

Operating Temperature –20°C to 50°C6
Operating Humidity (RH) Up to 100%, condensing
Storage Temperature –20°C to 30°C, up to 95% RH, non-condensing, State of Energy (SOE): 25% initial
Maximum Elevation 3000 m
Environment Indoor and outdoor rated
Enclosure Rating IP55
Ingress Rating IP67 (Battery & Power Electronics)
IP55 (Wiring Compartment)7
Pollution Rating PD3
Operating Noise @ 1 m < 50 db(A) typical, <62 db(A) maximum

6Powerwall 3 is designed to operate in all climates from temperatures of -20°C to 50°C. Performance may be de-rated at operating temperatures above 40°C.

7All wiring entry ports are DVC Class C.

Compliance Information

Safety

IEC 62477-1: 2022 - Safety requirements for power electronic converter systems and equipment - Part 1: General

IEC 62109-1:2010 - Safety of power converters for use in photovoltaic power systems - Part 1: General requirements

IEC 62109-2: 2011 - Safety of power converters for use in photovoltaic power systems - Part 2: Particular requirements for inverters

IEC 62933-5-2: 2020 - Electrical energy storage (EES) systems - Part 5-2: Safety requirements for grid-integrated EES systems - Electrochemical-based systems

IEC 62619: 2022 - Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications

UL9540A: Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems

Grid Interoperability

G98 Issue 1 - Amd 7 - Oct 2022 - Requirements for the connection of Fully Type Tested Micro-generators (up to and including 16 A per phase) in parallel with public Low Voltage Distribution Networks on or after 27 April 2019

G99 Issue 1 - Amd 9 - Oct 2022 - Requirements for the connection of generation equipment in parallel with public distribution networks on or after 27 April 2019

G100 Issue 2 - Amd 2 - Technical Requirements for Customer's Export and Import limitation Schemes

EMC

IEC 61000-6-1:2016 - Electromagnetic compatibility (EMC) - Part 6-1: Generic standards - Immunity standard for residential, commercial and light-industrial environments

EN IEC 61000-6-3: 2020 - Electromagnetic compatibility (EMC) - Part 6-3: Generic standards - Emission standard for equipment in residential environments