Grid Supply Fuse and Fuse Holder
The grid supply fuse and fuse holder are installed during Make AC Power Connections to Supply and Load Panels.
Note
The 'type aM' fuse ensures 16
kA short circuit current protection per DNO requirements. Without this fuse,
the Gateway is rated to a 10 kA short circuit current. If replacing fuses or
breakers, they must be of equivalent trip/open and short circuit ratings and
CE marked.
Note
For single-phase sites, a
single 100 A fuse is required and for 3-phase sites three (3) 80 A fuses are
required. Fuses should comply with BS 88.3, type aM, 22x58mm cartridge
fuse.