Backup Gateway 2 Wiring

Terminal Name | Recommended Wire Color | Wire Size | |
---|---|---|---|
A | Ethernet terminal - not used, see Ethernet Jacks | ||
B | Earth Bar | Green or Green/Yellow | 2.5 – 25 mm2 |
C | Grid Supply (L1, L2, L3, N) | Brown, Black, Grey, Blue | 2.5 – 35 mm2 |
D | Backup Loads and Generation (L1, L2, L3, N) | Brown, Black, Grey | 2.5 – 35 mm2 |
E | Generation Neutral Bar (N) | Blue | 2.5 – 25 mm2 |
F | Non-Backup Loads and Non-Backup Generation (L1, L2, L3, N) | Brown, Black, Grey, Blue | 2.5 – 35 mm2 |
G | Switched Neutral-Earth link | - |
16 mm 2 |