Tesla Remote Energy Meter Specifications
Tesla Remote Energy Meter Specifications
Model Number | 2002069-00-x |
Accuracy | 0.5% (ANSI C12.1) |
Nominal AC Voltage | 100 - 240 VAC 1 |
AC Frequency | 50 - 60 Hz |
Maximum Power Consumption | 3 W |
Compatible CTs | Tesla 200A CTs (see Tesla 200A CT Specifications) |
Connection Method | Wireless: Wi-Fi (2.4 and 5 GHz) 2, 5 |
Wired: RS-485 harness (1.2 m or 4 ft) 3, 4, 5 | |
Overcurrent Protection Device (OCPD) | 15A |
Dimensions | 145 x 52 x 31 mm (5.7 x 2 x 1.2 in) |
Ambient Operating Temperature | –30°C to 70°C (-22°F to 158°F) |
Conforms to | UL 61010-1, CSA C22.2 No. 61010-1, IEC/EN 61010-1, ANSI C12.1, IEC 62052-11, IEC 62053-21 |
Supported Applications | Site, Solar, Generator, Conductor |
Compatible Grid Types | 1ф L1-N, Split Phase L1-L2-N, 3ф L1-L2-L3-N Wye 6 |
1 Voltage harness (600 mm or 23.6 in) is included in the Tesla Remote Energy Meter kit. If additional length is required, the voltage harness can be extended using 16-10 AWG (1.5 - 6 mm2) AC wiring. To maintain accuracy for revenue grade metering (RGM), keep the meter within 61 m (200 ft) of its breaker when using 14 AWG (2.5 mm2) wire.
2 An external Wi-Fi antenna and antenna extension cable are included in the Tesla Remote Energy Meter kit. When using Wi-Fi as the connection method, remote meters placed inside of load centers can be subject to signal interference, especially when a panel cover is installed. For best performance, where possible, use the included external antenna and the antenna extension cable to extend the external antenna.
3 RS-485 harness is not included in the Tesla Remote Energy Meter kit; it can be ordered individually (Tesla P/N 2045794-00-x).
4 If the RS-485 harness length is not sufficient, 24 - 16 AWG (0.2 - 1.5 mm2) communication wiring can be used to extend the length up to a maximum of 100 m or 328 ft.
5 A Powerwall 3 site can have a maximum of (2) Tesla Remote Energy Meters; (1) connected via RS-485 harness for measuring the site and another (1) connected via Wi-Fi for measuring the AC-coupled solar. Do not connect (2) Tesla Remote Energy Meters via Wi-Fi.
6 Connection to L1 and Neutral is always required.
Tesla 200A CT Specifications
Model Number | 2033376-00-x |
Capacity | 200 A |
Insulation Rating | 600 V |
Lead Length | 1.5 m (59 in)7 |
Optional Extension | 3.5 m (138 in)8 |
Optional Y-Splitter | Not available |
Dimensions (L, W, H) | 86 x 55 x 18 mm (3.4 x 2.2 x 0.7 in) |
Window Size | 24 mm (0.98 in) |
Operating Temperature | –30°C to 85°C (-22°F to 185°F) |
7 If the CT lead length is not sufficient, do not splice the CT leads. Up to (2) CT extensions can be used to extend the length to a maximum of 8.5 m (1.5 m CT lead + 3.5 m extension + 3.5 m extension).
8 Extension is not included in the Tesla Remote Energy Meter kit; it can be ordered individually (Tesla P/N 2060713-xx-y).