Install Load / Generation Breakers on Internal Panelboard
The Gateway 3 internal panelboard can be used for generation sources and/or backup loads.
- Install listed breakers on the
internal panelboard, noting the phasing (top position is L2).NoteSee Acceptable Circuit Breakers for all acceptable branch circuit breakers.NoteIf there are non-generation loads on the internal panelboard, Tesla recommends installing breakers in the following order:
- Solar breaker(s) in the top breaker slots
- Powerwall breaker(s)
- Wall Connector breaker(s)
- Load breaker(s) in any remaining breaker slots at the bottom
- For each breaker, connect the accompanying Neutral to the Neutral bar, and the
accompanying Ground to the Ground bar.
- After the breakers are installed,
insert the top of the hold-down bracket into the opening above the internal
panelboard. Fasten the bottom of the hold-down bracket using the provided T20
Torx head screw.NoteThe breaker hold-down is used to mechanically secure back-fed breakers onto the internal panelboard. The breaker hold-down kit may be required by the local authority having jurisdiction.
Internal Panelboard Design Considerations
The internal panelboard is a 200 A-rated bussing that supports 8x 1-inch breaker spaces (16 circuits) using branch circuit breakers up to 125 A maximum.
Note
These breakers serve as circuit
protection for the equipment. Breaker sizing and installation must comply with the
National Electric Code.
Note
The Gateway
3 utilizes a jumper bridge to
connect the internal panelboard to the backup lugs, as described in Appendix A:
Backup Lugs and highlighted in the image below. This jumper bridge can be
removed to install a disconnect before the internal panelboard (see Gateway 3 Wiring Diagrams for a wiring diagram).
The previous generation of Gateway, the Backup Gateway 2, required the installation of factory-made jumpers to supply power to the internal panelboard; the installer could choose to connect the internal panelboard to either the Backup or Non-Backup terminals.