Single Powerwall+ to Powerwall 3 Upgrade
Overview
This procedure outlines the steps for replacing a single Powerwall+ system with a single Powerwall 3 system.
| Existing Equipment | Replacement Equipment | Scope of Work | Current / Power Output Setting |
|---|---|---|---|
| Single Powerwall+ | Single Powerwall 3 | Reuse existing 50 A circuit | 32 A (7.6 kW) |
If the site has one or more Powerwall 2 units to be swapped, refer to the appropriate procedure below:
Prerequisites
- Confirm the original site is visible in Powerhub
- If the swap is being completed by a subcontractor company, ensure the site has been shared with that subcontractor company's Powerhub instance. See Site Sharing in the Powerhub User Manual for instructions to share a site
- Ensure the updated planset is available (indicating that a site redesign was completed). The new site design should be compliant with all existing permits, or re-permitted according to the new design
Hazards
Safety and PPE
- Safety glasses (ANSI Z87.1 or EN 166)
- Cut-resistant gloves (ANSI Cut Level 3 or EN 388 Level C)
- Safety rated shoes with leather upper
General Equipment
- Paint pen
Remove
- Complete the Powerwall+ Lockout/Tagout procedure to de-energize the system.
- Follow the Powerwall+ Solar Assembly Removal procedure to remove the PVI portion of the system from the wall.
- Follow the Removing Powerwall 2 procedure procedure to remove the Powerwall portion of the system from the wall.
-
Remove the screws securing the
Powerwall+ mounting bracket to the wall.
Remove the mounting bracket and clean the wall surface from any sealant or dirt.
- Patch the holes created from the mounting bracket hardware using a method suitable for the wall surface.
-
Remove the conduit fittings and
determine the changes needed in the conduit run to accommodate the new Powerwall.
In most cases where the run is short, the conduit should be removed and new conduit should be run.
In cases where the conduit can be reused or extended, make sure that the fittings are appropriate and all the connections are compliant with local code.
Install
-
Follow the instructions in Powerwall 3 Installation Manual with Backup Gateway 2 to install the new Powerwall 3.
-
If a Rapid Shutdown Device (RSD) is connected to the existing Gateway 2, it must be
connected to the Powerwall 3.
Follow the instructions in STEP 8: Install System Shutdown Switch Where Required in the Powerwall 3 Installation Manual to switch the RSD from the Gateway to the Powerwall 3. The jumper should be removed from the Powerwall 3 and installed in the RSD port of the Gateway 2, from which the switch wire was removed.
-
Once all conductors are installed,
follow these steps to commission the new unit.
NoteDo NOT complete the Powerwall 3 commissioning procedure outlined in the Powerwall 3 Install Manual. Instead, use the steps provided below which detail several deviations from the standard commissioning procedure.
-
Turn on the Powerwall 3 switch and
connect to it using the Device
Setup interface in Tesla One app.
NoteAfter turning on the unit, allow 2 - 3 minutes for the Wi-Fi signal to begin broadcasting.
-
Navigate to the Networking tab and connect the unit
to the customer's Wi-Fi, if available. Refer to Configure Internet Connection section in the Powerwall 3 Quick Guide for more information.
-
On the Software tab, check for software
updates and download any available updates.
-
Navigate to the System tab and verify that the
Gateway is communicating with the Powerwall 3 without any errors. If the communication
is not established, inspect the CAN wiring between the units.
Refer to the Check Connected Devices page for more information.
-
Set the Powerwall's maximum
power/current output to 32 A (7.7 kW) using instructions in the Configure Powerwall 3 Maximum Power / Current Output section.
WarningThis step is critical. Failure to complete it can result in electrical faults in the wiring due to overcurrent. Do NOT start the system before setting this limit.
-
Document the configured limit on the
product label on the left side of the Powerwall unit. Use a paint pen to mark the box to
show the current has been limited to 32 A.
-
Navigate to the Metering tab to confirm the
meter(s) are configured correctly. Powerwall 3 only supports Tesla Remote Meters or
wired meters, so any third-party meters, such as Neurio meters, must be replaced with a
Tesla Remote Meter.
Replace meters as necessary and configure them in the Metering tab using the instructions in the Configure Meters and CTs section.NoteReplacing a meter with a Tesla Remote Meter is common at sites with AC-coupled solar or non-backup loads. Follow this guidance to correctly set up the meters: Install Tesla Remote Energy Meter and CTs.NoteIf Meter Y is used in the Gateway, it does not need to be replaced.
-
Navigate to the Settings tab to set the grid code
and solar installation type. If the site requires additional settings, set those under
the Advanced Settings option.
Refer to Configure Settings for more information.
-
Complete the Installer Registration as follows:
-
Complete the Customer Registration as follows:
NoteCustomer registration is the action that triggers the API call to the cloud, which transmits the new device configuration for the site. This will ensure the customer can see the updated site in their Tesla Mobile App, and the Partner(s) can see the correct device in Powerhub.
-
Start the system.
-
Before leaving the site, inform the
homeowner that their unit has been replaced with a Powerwall 3, and that the device
configuration will update overnight. They will see the new data and can control their
new Powerwall 3 starting the following morning.
Additionally, advise the customer that some app settings might have been reset with the swap and to check their configurations if they have been changed from default values.
Confirm Site Updates in Powerhub
- Confirm the new Powerwall 3 now
appears in the Devices list in
Powerhub
- The new Powerwall 3 will appear
instantly after registration
- Note that Powerhub and the customer's Tesla App will not display data (telemetry or settings info) from the new Powerwall 3 right away. This data will appear after the overnight sync
- The new Powerwall 3 will appear
instantly after registration
- Note that the old Powerwall+ will
still appear in the Devices list
- Powerhub will consider this device "Deactivated" after 30 days of no communication
- Note that this will not impact the customer's app experience, telemetry, or ability to control their Powerwall 3
- Once the 30-day period has passed and the Powerwall+ has been automatically deactivated, it will no longer appear in the Devices list in Powerhub