Powerwall Specifications
Tesla AC Powerwall with Gateway 2.0 is certified for Performance category A & B with Abnormal categories II & III.
For full compliance to IEEE 1547-2018 and IEEE 1547.1-2020 GW.0 with SMC shall be used with ACPW.
Performance Specifications
AC Voltage (Nominal) | 120/240 V |
Feed-In Type | Split Phase |
Grid Frequency | 60 Hz |
Total Energy1 | 14 kWh |
Usable Energy1 | 13.5 kWh |
Real Power, Max Continuous (On-Grid) | 5 kW (charge and discharge) |
Real Power, Max Continuous (Off-Grid) | 7 kW |
Real Power, Peak (10 s, Off-Grid/Backup) | 10 kW (charge and discharge) |
Apparent Power, Max Continuous | 5.8 kVA (charge and discharge) |
Apparent Power, Peak (10 s, Off-Grid/Backup) | 10 kVA (charge and discharge) |
Maximum Continuous Current | 24 A |
Maximum Output Fault Current | 70 A |
Overcurrent Protection Device | 30 A |
Surge withstand Voltage on AC Ports | 4kV |
Surge withstand Voltage on Communication Ports | 2kV |
Radiated RF Immunity | 35V/m |
Imbalance for Split-Phase Loads | 100% |
Power Factor Output Range | +/– 1.0 adjustable |
Power Factor Range (full-rated power) | +/– 0.85 |
Internal Battery DC Voltage | 50 V |
Maximum Short-Circuit Current Rating | 10 kA |
Round Trip Efficiency1,2 | 90% |
Connection / Reconnection Range | 0 - 600 s |
1 Values provided for 25°C (77°F), 3.3 kW charge/discharge power.
2 AC to battery to AC, at beginning of life.
Mechanical Specifications
Dimensions | 1150 mm x 753 mm x 147 mm (45.3 in x 29.6 in x 5.75 in) |
Weight | 114 kg (251.3 lbs) |
Mounting | Floor or wall mount |
Environmental Specifications
Operating Temperature | –20°C to 50°C (–4°F to 122°F)4 |
Operating Humidity (RH) | Up to 100%, condensing |
Storage Conditions | –20°C to 30°C (–4°F to 86°F) |
Up to 95% RH, non-condensing | |
State of Energy (SoE): 25% initial | |
Maximum Elevation | 3000 m (9843 ft) |
Environment | Indoor and outdoor rated |
Enclosure Type | NEMA 3R |
Ingress Rating | IP67 (Battery & Power Electronics) |
IP56 (Wiring Compartment) | |
Wet Location Rating | Yes |
Noise Level @ 1m | < 40 dBA at 30°C (86°F) |
4Performance may be de-rated at operating temperatures below 10°C (50°F).
Compliance Information
Specification | Standard certified |
---|---|
Safety | UL 1741:2021 Ed.3 Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources |
Power Conversion Equipment [CSA C22.2#107.1:2016 Ed.4] | |
Grid Interoperability | UL 1741SB Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources |
IEEE 1547: 2018 - IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces | |
IEEE 1547.1:2020 IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces | |
Supplement SA to UL 1741 - Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources [UL 1741:2010 Ed.2 (Supplement SA)+R:15Feb2018] | |
With the source requirements document (SRD) v2.0–Hawaii Rule No. 14H Interconnection of Distributed Generating Facilities with the Company’s Distribution System Effective: |
|
CSA C22.3#9:2020 Ed.2 Interconnection of distributed energy resources and electricity supply systems | |
Energy Storage | Energy Storage Systems and Equipment [ANSI/CAN/UL 9540:2020 Ed.2] |
EMC | IEEE 1547.1 (2020), IEEE C37.90.1:2012, IEEE C62.41.2:2002 |