Current Transformer Capacity
Standard Neurio CTs have a capacity of 200 A.
If the wiring configuration allows, it is possible to pass multiple conductors of the same type through a single CT, provided the sum of the conductor’s current ratings does not exceed the CT current handling capacity. This is especially useful for systems with multiple solar inverters.

If a site has multiple solar inverters spaced far apart, or if a main panel has two main breakers (for example, 400 A service with two 200 A breakers), a Y-splitter cable (for Neurio W1 meters: Tesla P/N 1129625-00-x, for Neurio W2 meters: Tesla P/N 1622286-xx-y) can be used to connect two CTs on the same phase to a single meter port.

For the Neurio W1 meter, 800 A CTs are also available for larger service sizes (Tesla P/N 1447689-00-x). The 800 A CTs can only be used with the Neurio W1 meter, and the 800 A CT option must be selected during device setup from a drop down menu on the Meter page.