Voltage Tap and Current Transformer Connections
Voltage taps and current transformers must be connected so they are measuring the same phase. They must correspond according to the following table and diagram:


Phase | Meter Voltage Tap Port | Meter CT Port |
---|---|---|
Solar L1 | A | 1/A |
Solar L2 | B | 2/B |
Solar L2 | B/C* | 3/C |
Solar L1 | A | 4/A |
*With combined leads in voltage line harness, ports B and C are equivalent (correspond to L2).