Appendix B: Available Device-Level Signals
Note that device-level signals are only available via the UI and the Bulk Telemetry endpoint (see Telemetry Bulk API).
Powerwall and Solar Inverter
UI Name | API Name | Relevant Product Variants | Description | Unit |
---|---|---|---|---|
AC Voltage | inverter_voltage_ac | Powerwall 2, Powerwall+, Powerwall 3, Solar Inverter | Voltage measured at the inverter terminals. | V |
solar_inverter_voltage_ac | ||||
AC Voltage L1-G | solar_inverter_voltage_ac_l1_ground | Solar Inverter | AC voltage measured between line 1 and Ground at the inverter terminals. | V |
AC Voltage L2-G | solar_inverter_voltage_ac_l2_ground | Solar Inverter | AC voltage measured between line 2 and Ground at the inverter terminals. | V |
Ambient Temperature | ambient_temp | Powerwall 2, Powerwall+, Powerwall 3 | Ambient temperature measured by sensor on Powerwall air intake. | °C |
Current MPPT A | inverter_current_mppt_a | Powerwall+, Powerwall 3, Solar Inverter | Current produced by the string of solar modules connected to MPPT A. | A |
solar_inverter_current_mppt_a | ||||
Current MPPT B | inverter_current_mppt_b | Powerwall+, Powerwall 3, Solar Inverter | Current produced by the string of solar modules connected to MPPT B. | A |
solar_inverter_current_mppt_b | ||||
Current MPPT C | inverter_current_mppt_c | Powerwall+, Powerwall 3, Solar Inverter | Current produced by the string of solar modules connected to MPPT C. | A |
solar_inverter_current_mppt_c | ||||
Current MPPT D | inverter_current_mppt_d | Powerwall+, Powerwall 3, Solar Inverter | Current produced by the string of solar modules connected to MPPT D. | A |
solar_inverter_current_mppt_d | ||||
Current MPPT E | inverter_current_mppt_e | Powerwall 3 | Current produced by the string of solar modules connected to MPPT E. | A |
Current MPPT F | inverter_current_mppt_f | Powerwall 3 | Current produced by the string of solar modules connected to MPPT F. | A |
Energy Produced MPPT A | inverter_energy_mppt_a | Powerwall+, Powerwall 3, Solar Inverter | Energy produced by the string of solar modules connected to MPPT A. | Wh |
solar_inverter_energy_mppt_a | ||||
Energy Produced MPPT B | inverter_energy_mppt_b | Powerwall+, Powerwall 3, Solar Inverter | Energy produced by the string of solar modules connected to MPPT B. | Wh |
solar_inverter_energy_mppt_b | ||||
Energy Produced MPPT C | inverter_energy_mppt_c | Powerwall+, Powerwall 3, Solar Inverter | Energy produced by the string of solar modules connected to MPPT C. | Wh |
solar_inverter_energy_mppt_c | ||||
Energy Produced MPPT D | inverter_energy_mppt_d | Powerwall+, Powerwall 3, Solar Inverter | Energy produced by the string of solar modules connected to MPPT D. | Wh |
solar_inverter_energy_mppt_d | ||||
Energy Produced MPPT E | inverter_energy_mppt_e | Powerwall 3 | Energy produced by the string of solar modules connected to MPPT E. | Wh |
Energy Produced MPPT F | inverter_energy_mppt_f | Powerwall 3 | Energy produced by the string of solar modules connected to MPPT F. | Wh |
Frequency | battery_inverter_frequency | Powerwall 2, Powerwall+, Powerwall 3, Solar Inverter | Frequency measured at the inverter terminals. | Hz |
Power MPPT A | inverter_power_mppt_a | Powerwall+, Powerwall 3, Solar Inverter | Power produced by the string of solar modules connected to MPPT A. | W |
solar_inverter_power_mppt_a | ||||
Power MPPT B | inverter_power_mppt_b | Powerwall+, Powerwall 3, Solar Inverter | Power produced by the string of solar modules connected to MPPT B. | W |
solar_inverter_power_mppt_b | ||||
Power MPPT C | inverter_power_mppt_c | Powerwall+, Powerwall 3, Solar Inverter | Power produced by the string of solar modules connected to MPPT C. | W |
solar_inverter_power_mppt_c | ||||
Power MPPT D | inverter_power_mppt_d | Powerwall+, Powerwall 3, Solar Inverter | Power produced by the string of solar modules connected to MPPT D. | W |
solar_inverter_power_mppt_d | ||||
Power MPPT E | inverter_power_mppt_e | Powerwall 3 | Power produced by the string of solar modules connected to MPPT E. | W |
Power MPPT F | inverter_power_mppt_f | Powerwall 3 | Power produced by the string of solar modules connected to MPPT F. | W |
On/Off Switch | powerwall_switch_state | Powerwall 2, Powerwall+, Powerwall 3 | State of the On/Off switch found on the side of the Powerwall. | Text |
Reactive Power | battery_inverter_reactive_power | Powerwall 2, Powerwall+ | Instantaneous reactive power measured at the inverter terminals. | VAR |
Real Power | battery_inverter_real_power | Powerwall 2, Powerwall+, Powerwall 3, Solar Inverter | Instantaneous real/active power measured at the inverter terminals. | W |
Real Power RGM | device_inverter_instant_power_rgm | PW3 | Instantaneous real/active power measured at the inverter's Revenue Grade Meter (RGM). | W |
Energy Produced RGM | device_inverter_energy_exported_rgm | PW3 | Energy generated by the solar system and/or discharged by the battery. Measured at the inverter's Revenue Grade Meter (RGM). | Wh |
Energy Consumed RGM | device_inverter_energy_imported_rgm | PW3 | Energy consumed by the battery. Measured at the inverter's Revenue Grade Meter (RGM). | Wh |
Total Solar Energy Produced | inverter_energy | Powerwall+, Powerwall 3, Solar Inverter | DC Energy generated by the solar system. Sum of the energy produced by each MPPT. | Wh |
solar_inverter_energy | ||||
Voltage MPPT A | inverter_voltage_dc_mppt_a | Powerwall+, Powerwall 3, Solar Inverter | DC voltage of the string of solar modules connected to MPPT A. | V |
solar_inverter_voltage_dc_mppt_a | ||||
Voltage MPPT B | inverter_voltage_dc_mppt_b | Powerwall+, Powerwall 3, Solar Inverter | DC voltage of the string of solar modules connected to MPPT B. | V |
solar_inverter_voltage_dc_mppt_b | ||||
Voltage MPPT C | inverter_voltage_dc_mppt_c | Powerwall+, Powerwall 3, Solar Inverter | DC voltage of the string of solar modules connected to MPPT C. | V |
solar_inverter_voltage_dc_mppt_c | ||||
Voltage MPPT D | inverter_voltage_dc_mppt_d | Powerwall+, Powerwall 3, Solar Inverter | DC voltage of the string of solar modules connected to MPPT D. | V |
solar_inverter_voltage_dc_mppt_d | ||||
Voltage MPPT E | inverter_voltage_dc_mppt_e | Powerwall 3 | DC voltage of the string of solar modules connected to MPPT E. | V |
Voltage MPPT F | inverter_voltage_dc_mppt_f | Powerwall 3 | DC voltage of the string of solar modules connected to MPPT F. | V |
Wiring Compartment Temperature | wiring_compartment_ambient_temp | Powerwall 2, Powerwall+ | Temperature measured inside of the wiring compartment | °C |