DC-coupled solar (connected directly to Powerwall 3) is strongly preferred over AC-coupled solar for the following reasons:
Less equipment required for
DC-coupled solar, resulting in reduced system cost
Increased efficiency for DC-coupled solar
Low energy management during a grid
outage
In some scenarios, it is difficult or not feasible to avoid systems with AC-coupled
solar. Most commonly, this occurs when Powerwall 3 is installed on a system with
existing AC-coupled solar. As shown below, solar can be installed alongside Powerwall 3 solar, or with Powerwall 3 as storage only.
Note
Powerwall 3 can also be used without any
solar on the site.
Figure 1. Powerwall 3 with AC and DC Coupled
SolarFigure 2. Powerwall 3 with AC Coupled Solar (Storage
Only)
PV to Powerwall Ratio
For systems with AC-coupled solar only, a maximum of 5 kW AC per Powerwall is allowed in
the backup circuit (the smaller of AC inverter rating or DC system size1).
1The 5 kW PV to Powerwall ratio was put
in place to protect the Powerwall system from excessive PV power during a grid outage. 5 kWis used because it is a common solar
inverter size,
allowing more PV systems to be fully backed up without needing to be split apart,
and inverters don’t always produce their maximum power. This ratio does not prevent
all issues; Powerwall’s maximum charge rate is 5
kW under ideal conditions (notably
operating temperature). If there is more than 5
kW of excess PV per Powerwall, the
system will frequency shift to try to reduce PV power, and may have to shut PV
production down completely.
Note
The AC-coupled PV to Powerwall
ratio and the maximum DC solar system sizing are independent of each other. See
Powerwall 3 DC System Sizing for
information about sizing the Powerwall 3 DC system.
CAUTION
Exceeding the PV to
Powerwall ratio may result in high fault current during a grid outage, which creates a serious risk of damage to Powerwall and/or the
customer's home loads. If a Powerwall is damaged by high fault current due to excess
PV during an outage, it will be out of warranty.
Options to avoid exceeding the ratio:
Increase number of Powerwalls
on site
Utilize Powerwall 3 for all PV on
site to avoid PV to Powerwall ratio
Split PV Inverter Point of
Interconnection, In / Out of the A Powerwall 3 site can
have a maximum of three Tesla Remote Energy
Meters: one
connected via RS-485 and up to two connected via Wi-Fi. (confirm with local electrical regulator that this practice
is accepted)
Downsize PV to meet
ratio
Shed part of the PV system
using grid dependent relays/contactors
Note
The 5 kW PV to Powerwall ratio can be applied to
any Powerwall unit in the system, including Powerwall 3. For example, a 5 kW third party solar inverter can be backed
up with a single Powerwall 3, as the ratio rule does not
apply to the solar inverter portion of the Powerwall 3.