Design Considerations

Supported Configurations

  • Up to (4) Powerwall 3 units can be installed with (1) Backup Gateway 2, with or without AC-coupled solar (see Appendix E: Installing Multiple Powerwall 3 Units and/or Expansion Units)
  • Up to (3) Expansion units can be connected to the Leader Powerwall 3 (see Appendix E: Installing Multiple Powerwall 3 Units and/or Expansion Units)
    Informational PurposesAn informational icon, calling your attention
    Note
    Do not connect Expansion units to a Follower Powerwall 3 unit.
  • Only Tesla devices are compatible with Powerwall 3; no third-party equipment in lieu of Backup Gateway 2 or Tesla Remote Energy Meter
  • Powerwall 3 is not compatible with the following:
    • Neurio remote energy meters (see Energy Metering for more information)
    • Other batteries (Powerwall 2 or third party batteries)
    • Stacked units (Powerwall 3 must be mounted in a side-by-side configuration)
    • Third party MLPE solutions, such as optimizers, installed on the DC-coupled solar system. These devices may lead to erratic system behavior such as nuisance tripping on the Powerwall 3 when installed on the DC-coupled solar system. However, they can be installed on the AC-coupled solar system.

System Tie-in

  • Backup systems must be one of the following:
    • 230 V single phase service
      • 100 A or smaller service, or (in absence of a service rating) maximum 100 A of loads downstream of Backup Gateway 2
    • 230 / 400 V three phase service
      • 80 A or smaller service, or (in absence of a service rating) maximum 80 A of loads downstream of Backup Gateway 2
      • Follow all local requirements for balancing the system equally across the available phases
      Informational PurposesAn informational icon, calling your attention
      Note
      Regardless of the number of Powerwalls installed, only one phase (L1, L2, or L3) will provide backup during a grid outage.
  • A breaker is always required for Powerwall tie in. This breaker serves as an overcurrent protection device for Powerwall and must be wired in accordance with local wiring codes and regulations. See Powerwall 3 Specifications section for breaker size.
    Informational PurposesAn informational icon, calling your attention
    Note
    In line with relevant standards, Powerwall must be wired to support the maximum continuous current of the system.
  • Powerwall 3 must always be connected to the Home terminals downstream of the Backup Gateway 2
  • Recommend that total Powerwall supply is able to power the single largest automatic load in the backup circuit
  • Any/all loads on the backup circuit are adequately protected with an overcurrent protection device
  • All three phase loads or solar must be excluded from the backup circuit
  • All single phase loads in the backup circuit must be sized appropriately for the configured power output of the Powerwall (see Powerwall 3 Specifications for power output options)
  • Site and solar monitoring must be installed to capture overall power flow to/from the site, as well as all solar production (see Energy Metering)
  • Powerwall and Backup Gateway 2 are rated for 10 kA of fault current.

Powerwall 3 Solar

Powerwall 3 has an integrated inverter and 3 MPPTs, with a maximum solar input of 20 kW DC.

Informational PurposesAn informational icon, calling your attention
Note
See AC-Coupled Solar System Sizing for information about sizing AC-coupled solar with Powerwall 3.