STEP 11: Turn On and Commission the System

Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Before terminating any conductors inside Powerwall 3, ensure that the integrated DC isolator and Powerwall 3 On/Off switch are both turned OFF to de-energize the system. Confirm lack of voltage at the AC and PV terminals before proceeding.

Prepare the System for Commissioning

Powerwall Installation Complete? Solar Installed? Powerwall 3 On / Off Switch Integrated DC Isolator Powerwall 3 Breaker Commissioning
No (no AC service, install crew unable to complete, etc.) No Leave the Powerwall 3 switch OFF
Leave the integrated DC isolator OFF
Leave the Powerwall 3 breaker OPEN (OFF) Commissioning cannot be completed at this time
Yes No Leave the Powerwall 3 switch ON
Leave the integrated DC isolator OFF
Leave the Powerwall 3 breaker CLOSED (ON)

See Commission the System Ahead of Solar Installation

Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Turn the Powerwall 3 switch OFF to de-energize the system terminating any conductors inside Powerwall 3. Confirm lack of voltage at the AC and PV terminals before proceeding.
Yes Yes Leave the Powerwall 3 switch ON
Leave the integrated DC isolator ON
Leave the Powerwall 3 breaker CLOSED (ON) See Commission the System After Powerwall and Solar Installation