Backup Gateway 2 Communication Wiring

Table 1. Powerwall Communication Wiring
Terminal Name Recommended Wire Color Wire Size
1 12V + (Logic +) Red

1.5 mm2 (max 45 m)
1.0 mm2 (max 35 m)

2 GND (Earth) Black
3 CN + (CAN HI) Blue 0.2 - 1.5 mm2
4 CN – (CAN LO) Orange

Informational PurposesAn informational icon, calling your attention
Note
4-conductor communication cable must be 300 V rated or double insulated with one twisted pair shielded copper cable.
Table 2. Aux Wiring
Terminal Name Recommended Wire Color Wire Size
1 Site Shutdown (OUT) - 0.2 - 1.5 mm2
2 Site Shutdown (IN) - 0.2 - 1.5 mm2
3 Generator / Load Control (+) Red 0.2 - 1.5 mm2
4 Generator / Load Control (-) Black 0.2 - 1.5 mm2
5 Interlock pin - 0.2 - 1.5 mm2