Backup Gateway 2 Specifications
Backup Gateway 2 Electrical Specifications
AC Voltage (Nominal) | 230 V (Line-to-Neutral) |
400 V (Line-to-Line) | |
Feed-In Type | Single Phase, Three Phase |
Grid Frequency | 50 Hz |
Maximum Overcurrent Protection Device | 100 A (single-phase service) |
80 A (2- and 3-phase service) | |
Maximum Input Short Circuit Current | 10 kA |
Overvoltage Category | Category III |
AC Meter | Revenue accurate (+/– 0.2 %)1 |
Safety | IEC 61439-1, IEC 61439-3 |
1Revenue accurate when using Gateway internal site meter. |
Note
Refer to circuit breaker datasheet
for rated peak withstand current (Ipk) and associated duration.
Environmental Specifications
Operating Temperature2 | –20°C to 50°C |
Operating Humidity (RH) | Up to 100%, condensing |
Maximum Altitude | 3000 m |
Ingress Rating | IP55 |
Environmental Category | Indoor and outdoor rated |
Wet Location Rating | Yes |
Pollution Degree | PD2 |
2 Performance may be de-rated in extreme ambient temperatures |
Mechanical Specifications
Height | 584 mm |
Width | 380 mm |
Depth | 127 mm |
Weight | 11.4 kg |