Backup Gateway 2 Specifications

Backup Gateway 2 Electrical Specifications

AC Voltage (Nominal) 230 V (Line-to-Neutral)
400 V (Line-to-Line)
Feed-In Type Single Phase, Three Phase
Grid Frequency 50 Hz
Maximum Overcurrent Protection Device 100 A (single-phase service)
80 A (2- and 3-phase service)
Maximum Input Short Circuit Current 10 kA
Overvoltage Category Category III
AC Meter Revenue accurate (+/– 0.2 %)1
Safety IEC 61439-1, IEC 61439-3
1Revenue accurate when using Gateway internal site meter.
Informational PurposesAn informational icon, calling your attention
Note
Refer to circuit breaker datasheet for rated peak withstand current (Ipk) and associated duration.

Environmental Specifications

Operating Temperature2 –20°C to 50°C
Operating Humidity (RH) Up to 100%, condensing
Maximum Altitude 3000 m
Ingress Rating IP55
Environmental Category Indoor and outdoor rated
Wet Location Rating Yes
Pollution Degree PD2
2 Performance may be de-rated in extreme ambient temperatures

Mechanical Specifications

Height 584 mm
Width 380 mm
Depth 127 mm
Weight 11.4 kg