Appendix F: Shutting Down Powerwall 3
Powerwall 3 system shutdown for emergency response or maintenance requires system shutdown and disabling solar output.
CAUTION
Open all third party
solar inverter breakers or handled disconnects before shutting down the Powerwall 3 system.
Safely Shut Down Powerwall 3 for Maintenance or Service
- Turn the Powerwall 3 On/Off switch OFF.
- Turn the Powerwall 3 integrated DC isolator switch OFF.
- Open the Powerwall 3 AC circuit breaker.
- Wait 30 seconds before proceeding
with any work. WarningRisk of electric shock from stored energy. Wait 30 seconds after disconnecting all sources of supply before proceeding.
- Use a lock-out device on the disconnecting means listed in the table below whenever performing work on equipment that is not within sight of the switch.
Disabling Solar, System Shutdown, and Disconnecting Means for Powerwall 3
Action | Powerwall 3 | AC-coupled Solar Inverter | |||
---|---|---|---|---|---|
On/Off Switch | Integrated DC Isolator | AC Breaker / Isolator | External DC Isolator | AC Breaker / Isolator | |
Disables DC-coupled Solar | Yes | Yes | No | Yes | No |
Disables AC-coupled Solar | No | No | No | No | Yes |
Disables AC Inverter (Input and Output) | Yes | No | Yes | No | No |
Isolates DC side for maintenance | No | No | No | Yes | Yes |
Isolates AC side for maintenance | No | No | Yes | No | No |