Tesla Asset Controller (TACO) Low Voltage and Communication Wiring
Communication Wiring to Backup Gateway 2
Note
Refer to local codes and standards for
correct wiring practices and wire colors.
Terminal Name | Recommended Wire Color | Wire Gauge | |
---|---|---|---|
1 | CN- (CAN LO) | Orange | 24 - 16 AWG (0.2 - 1.5 mm2) |
2 | CN+ (CAN HI) | Blue | 24 - 16 AWG (0.2 - 1.5 mm2) |
3 | GND (Earth) | Black | 18 - 16 AWG (0.2 - 1.5 mm2)* |
4 | 12V+ (Logic+) | Red | 18 - 16 AWG (0.2 - 1.5 mm2)* |
* The connector can accept wire gauges as small as 24 AWG, but the recommended minimum wire gauge is 18 AWG (0.8 mm2) due to potential voltage drop on long wire runs with smaller conductors.
Remote Energy Meter Wiring (Not Yet Available)
Note
The remote energy metering via an external meter is not yet supported.
Terminal Name | Recommended Wire Color | Wire Gauge | |
---|---|---|---|
5 | RS-485 + | Red | 24 - 16 AWG (0.2 - 1.5 mm2) |
6 | RS-485 - | Black | 24 - 16 AWG (0.2 - 1.5 mm2) |
Ethernet Jacks
Terminal Name | Recommended Wire Color | Wire Requirements | |
---|---|---|---|
7 | RJ45 Ethernet jacks | - | CAT5 or CAT6 Ethernet wiring (see Prepare Ethernet Wiring with RJ45 Connectors) |
Rapid Shutdown (RSD) Wiring
Terminal Name | Recommended Wire Color | Wire Gauge | |
---|---|---|---|
8 | Rapid Shutdown + | Red | 24 - 16 AWG (0.2 - 1.5 mm2) |
9 | Rapid Shutdown - | Black | 24 - 16 AWG (0.2 - 1.5 mm2) |
Note
The terminal between the two RSD
terminals is not used.
Aux Wiring (Not Yet Available)
Note
The load control functionality is not yet available.
Terminal Name | Recommended Wire Color | Wire Gauge | |
---|---|---|---|
10 | Load Control + | - | 24 - 16 AWG (0.2 - 1.5 mm2) |
11 | Load Control - | - | 24 - 16 AWG (0.2 - 1.5 mm2) |
TACO Low Voltage Harness
Terminal Name | Recommended Wire Color | Wire Gauge | |
---|---|---|---|
12 | TACO low voltage harness (provides 12V power to TACO) | - | - |