STEP 5: Make Powerwall 3 AC Circuit Connections

Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Before terminating any conductors inside Powerwall 3, ensure that the Enable switch is turned OFF to de-energize the system. Confirm lack of voltage at the AC and PV terminals before proceeding.
  1. Disconnect the AC circuit breaker of the main service disconnect and secure it against reconnection.
  2. Select the appropriate Powerwall 3 breaker size depending on the desired power / current output (configured in Tesla One):
    Table 1. Maximum Continuous Power / Current Options
    Maximum Continuous CurrentPower Output (AC)Breaker (Overcurrent Protection)

    48 A On-grid
    64 A Off-grid*

    11.5 kW On-grid
    15.4 kW Off-grid*

    80 A*
    48 A11.5 kW (default) 60 A
    41.7 A10 kW 60 A
    31.7 A7.6 kW 40 A
    24 A5.8 kW 30 A

    *Powerwall 3 can only provide 15.4 kW when off-grid and when there is sufficient solar; when the system is on-grid, and/or when solar production is insufficient, Powerwall 3 will provide 11.5 kW. If enabling this feature, Powerwall 3 must be installed with an 80 A breaker and appropriately sized conductors.

  3. (Conduit installations only) Run conduit as needed and attach the conduit fitting to the Powerwall 3 AC wiring knockout.
  4. Run the AC power conductors and the equipment grounding conductor from the main panel through the conduit or cable gland, pulling 24 inches (610 mm) of wiring into the enclosure. Route the conductors to the appropriate terminals, creating a service loop with the extra wiring (see Powerwall 3 AC Wiring for an example of a service loop).
    Warning IconA warning icon, calling your attention to a possibly risky situation
    CAUTION
    Any wire routing must be done through the wire management tabs at the top of the enclosure. Do not route loose wires through the front of the enclosure or over the Tesla Asset Controller.
  5. Connect the Powerwall 3 equipment grounding conductor:
    1. Strip the conductor insulation up to 3/4-inch (19 mm).
    2. Insert the grounding conductor in an equipment grounding terminal and tighten the screw in the Earth terminal to 35 in-lb (4 Nm).
      Informational PurposesAn informational icon, calling your attention
      Note
      It is best practice to connect the ground circuit before making any AC circuit connections.
  6. Connect the Powerwall 3 AC power conductors to the main panel or sub panel according to the electrical service type.
    Informational PurposesAn informational icon, calling your attention
    Note
    Each Powerwall 3 requires a circuit overcurrent protection device (see table above for required breaker size based on configured power output). This device serves as the disconnect for Powerwall 3 and must be wired in accordance with local wiring codes and regulations.
    Informational PurposesAn informational icon, calling your attention
    Note
    Tesla recommends a circuit breaker for overcurrent protection, as a circuit breaker can easily be reset by the homeowner if needed. As such, the required overcurrent protection device is referred to as the Powerwall 3 circuit breaker throughout this manual. Alternative overcurrent protection devices, such as a fused disconnect, may be used and may result in a poor customer experience if the homeowner cannot reset the system in the unlikely event of a trip.
    Warning IconA warning icon, calling your attention to a possibly risky situation
    CAUTION
    If using a fuse as the Powerwall 3 overcurrent protection device, it must be a Class RK1 Fast Acting fuse. Use one of the following fuses or equivalent:
    Fuse TypeManufacturerPart Number
    60 A Fast-Acting Fuse, Class RK1, >= 250VAC, CLFLittelfuseKLNR60
    Eaton / BussmannKTN-R-60
    Mersen / Ferraz ShawmutA2K60R
    40 A Fast-Acting Fuse, Class RK1, >= 250VAC, CLFLittelfuseKLNR40
    Eaton / BussmannKTN-R-40
    Mersen / Ferraz ShawmutA2K40R
    30 A Fast-Acting Fuse, Class RK1, >= 250VAC, CLFLittelfuseKLNR30
    Eaton / BussmannKTN-R-30
    Mersen / Ferraz ShawmutA2K350
  7. On the Powerwall 3 product label on the left side of the unit, use a paint pen, permanent marker, or similar to mark the configured power / current output.
    Informational PurposesAn informational icon, calling your attention
    Note
    If required, install a Power Control System (PCS) field marking label on the side of Powerwall 3 and mark the configured maximum current output on the label.
  8. If enabling 15.4 kW power when Powerwall 3 is off-grid, use a paint pen, permanent marker, or similar to mark the Powerwall 3 product label on the left side of the unit.
    Informational PurposesAn informational icon, calling your attention
    Note
    The Powerwall 3 power / current output must be configured as 11.5 kW (48 A) to enable 15.4 kW power when off-grid.
  9. Clear out any debris that may be present in the AC wiring terminals.
    Warning IconA warning icon, calling your attention to a possibly risky situation
    DANGER
    Metal debris like loose wires or metal shavings could create a high voltage risk when Powerwall is turned on.
  10. For each AC conductor:
    1. Strip the conductor insulation up to 7/16-inch (11 mm). Add a ferrule if the conductor is finely stranded.
    2. Insert the conductor as far as possible into the terminal.
      Warning IconA warning icon, calling your attention to a possibly risky situation
      Warning
      Ensure the conductors are inserted into the round terminals and not the rectangular slots. Inserting the conductors anywhere other than the round terminals will result in poor wire termination.
    3. Perform a pull test to ensure the conductor is fully seated in the terminal. Push the conductor back in after the pull test.
      Figure 1. Powerwall 3 AC Wiring
    4. After installing the AC conductors and equipment grounding conductor, gather them and secure them with the provided cable tie as shown above.
Informational PurposesAn informational icon, calling your attention
Note
If a conductor must be removed from the connector, insert a cabinet or electronics tip slotted screwdriver (up to 3/16-inch or 4.5 mm) into the actuation shaft to open the terminal. Pull the conductor free, then remove the screwdriver.
Figure 2. Spring Terminal with Screwdriver and Insert Conductor in Terminal

Required UL 1741 PCS Compliance Information

Informational PurposesAn informational icon, calling your attention
Note
The Tesla Powerwall 3 system is certified to UL 1741 PCS for the energy storage system (ESS) operating modes of import and export only. The installer can select three modes of operation for the system: No Site Export, PV Only Export, and PV, Battery Export.
  1. NO SITE EXPORT: The battery and solar will not export beyond the site meter, other than inadvertent export.
  2. PV ONLY EXPORT: The battery will not export beyond the site meter, other than inadvertent export. The export at the site meter will be limited to the export from as measured by the solar meter.
  3. PV, BATTERY EXPORT: The battery and solar will export beyond the site meter.
Informational PurposesAn informational icon, calling your attention
Note
To achieve UL 1741 PCS Import Only behavior, either PV ONLY EXPORT or NO SITE EXPORT must be selected. When the selected Grid Code applies to a region that requires UL 1741 PCS, such as California UL 1741 SA, the default setting is PV ONLY EXPORT. In the locally hosted Configuration Interface it is possible to further restrict the system to NO SITE EXPORT; however once set, it is not possible to change back to PV ONLY EXPORT. It is not possible to configure the system to allow BATTERY EXPORT in this mode.
Informational PurposesAn informational icon, calling your attention
Note
To achieve UL 1741 PCS Export Only behavior, PV, BATTERY EXPORT must be selected and the import rule must be set to charge only from solar (and not charge from the grid). When the selected Grid Code applies to a region that requires UL 1741 PCS, such as California UL 1741 SA, the default setting is PV ONLY EXPORT. In the locally hosted Configuration Interface it is possible to further restrict the system to NO SITE EXPORT; however once set, it is not possible to change back to PV ONLY EXPORT or PV, BATTERY EXPORT.
Informational PurposesAn informational icon, calling your attention
Note
This system is equipped with a power control system (PCS) which is suitably rated to provide branch circuit overcurrent protection. The controlled current setting shall not exceed the rating of any controlled busbars or conductor ampacity.
Informational PurposesAn informational icon, calling your attention
Note
The PCS controlled current setting for each PCS controlled conductor or bus bar shall be indicated with a field applied marking label on the conductor or in close proximity to the busbar.
Figure 3. PCS Field Marking Label
Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Only qualified personnel shall be permitted to set or change the setting of the maximum operating current of the PCS. The maximum PCS operating current setting shall not exceed the busbar rating or conductor ampacity of any PCS controlled busbar or conductor.
Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Configuration of power control settings system or changes to settings shall be made by qualified personnel only. Incorrect configuration or setting of the power control settings may result in unsafe conditions.
Informational PurposesAn informational icon, calling your attention
Note
The maximum operating currents in controlled busbars or conductors are limited by the settings of the power control system (PCS) and may be lower than the sum of the currents of the connected controlled power sources. The settings of the PCS controlled currents may be used for calculation of the design currents used in the relevant sections of NEC Article 690 and 705.
Informational PurposesAn informational icon, calling your attention
Note
Maximum PCS Controlled Current setting: 200 A.