Close Wiring Compartments
- Before closing any installed hardware, take photos of the completed wiring in the Powerwall, Backup Gateway 2, and main distribution board.
- Inspect the AC and PV wiring terminals to ensure all wire strands are properly inserted.
- Ensure that all conduit junctions and cable entry points are secure and properly sealed.
-
Install the Backup Gateway
deadfront panel and secure it firmly with the original screw. Mount the Backup
Gateway door, and latch it shut.
NoteIf the Backup Gateway is installed outdoors or in a high-traffic area, the latch can be locked shut.
- Arrange all wires neatly inside the Powerwall wiring compartment.
-
Install the air intake screen over the opening at the bottom of Powerwall,
ensuring it snaps into place.
- Clean the front edge of the Powerwall enclosure with a microfiber cloth to remove any debris that might interfere with the seal.
-
Carefully remove the glass front
cover from its packaging and, using a microfiber cloth, clean the sealing gasket
around the edge of the front cover to remove any debris that might interfere
with the seal.
CAUTIONTake extreme care when handling the sealing gasket. Damage to or contamination of the gasket or its mating surface could compromise Powerwall's ingress protection, resulting in product damage.
-
Carefully install the glass front cover:
- Clearly label all circuit breakers.