Performance Specifications
Continuous
Load Rating |
200A, 120/240V Split phase |
Short Circuit Current Rating |
22 kA with breaker1 |
Communication |
CAN |
AC
Meter |
+/- 0.5% |
1The breaker
size must be equal to or greater than the available fault current and can be
installed either upstream or downstream of the Backup Switch. This Backup Switch is
rated for use on a circuit delivering not more than 10,000 RMS symmetrical amperes,
300 V maximum. When used in conjunction with a circuit breaker rated not more than
200 A, the Backup Switch is rated for use on a circuit capable of delivering not
more than 22,000 RMS symmetrical amperes, 300V maximum, not in excess of circuit breaker
interrupting rating. Watthour meter not included in short circuit current
rating.
Compliance Information
Safety Standards |
USA: UL 414, UL 414 SB, UL 2735, UL 916, CA Prop
65 |
Emissions |
FCC Part 15, Class B, ICES 003 |
Mechanical Specifications
Dimensions |
6.9 x 8.1 x 2.9 inches (176 x 205 x 74
mm) |
Weight |
2.8 lb (1.27 kg) |
Meter and
Socket Compatibility |
ANSI Type 2S, ringless or ring type |
External Service Interface |
Contactor manual override2,
Reset button |
Conduit
Compatibility |
½-inch NPT |
2Manually
overrides the contactor position during a service event.
Environmental
Specifications
Operating Temperature |
–40°F to 122°F (–40°C to 50°C) |
Storage
Temperature |
–40°F to 185°F (–40°C to 85°C) |
Enclosure
Rating |
NEMA 3R |
Pollution
Rating |
PD3 |