Test PV Strings with MCIs

The following tests are performed on each PV string to confirm the PV wiring has been installed correctly and the array is functioning as expected:
Warning IconA warning icon, calling your attention to a possibly risky situation
Warning
Before connecting or disconnecting any PV strings:
  1. Ensure the Powerwall Enable switch is turned OFF.
  2. Ensure Powerwall is not connected to AC power.
  3. If an external PV disconnect means is available, open the external PV disconnect switch.
  4. Ensure that there is no voltage on the PV inputs of Powerwall 3.
Informational PurposesAn informational icon, calling your attention
Note
For each of the following tests, ensure the tester leads are connected to the correct conductor as described in the test instructions. If the polarity is swapped, for instance if the negative tester lead is connected to the positive conductor, the test results will be incorrect.

Required Tools

  • Standard DC voltage meter
  • Insulation Resistance tester (Tesla recommends the Klein ET600 tester)

Verify PV String Polarity

Required Tools:
  • Standard DC voltage meter or Insulation Resistance tester (Tesla recommends the Klein ET600 tester)

Testing Procedure:

  1. Set the voltage meter to DC test mode.
  2. Connect the voltage meter positive lead to the string's positive conductor.
  3. Connect the voltage meter negative lead to the string's negative conductor.
  4. On the voltage meter, push the TEST button.
  5. Confirm the result is a positive number. If the number is negative, string polarity has been swapped.
    Informational PurposesAn informational icon, calling your attention
    Note
    The voltage meter test result will not reflect the actual expected string voltage because there are MCIs installed in the string.

In the following diagram, the top image displays a multimeter correctly connected to the positive and negative leads in the PV array, resulting in a positive voltage (though this is NOT the string voltage). The bottom image displays an array where the positive and negative PV leads are swapped, resulting in a negative voltage test result. Correct the meter probe polarity and test again.

Informational PurposesAn informational icon, calling your attention
Note
The diagrams above illustrate example PV stringing configurations; the number of MCIs and where they are installed in the string varies by installation configuration.

Verify String Voltage

Required Tools:
  • Insulation Resistance tester (Tesla recommends the Klein ET600 tester)

Testing Procedure:

  1. Set the voltage meter to 1kV test mode.
  2. Connect the voltage meter positive lead to the string's positive conductor.
  3. Connect the voltage meter negative lead to the string's negative conductor.
  4. On the voltage meter, push the TEST button.
  5. Confirm the DC voltage result is equal to (or nearly equal to) the expected voltage per the system planset (it may not be the exact voltage).
    • If the DC voltage is significantly lower than the expected voltage, there is likely a wiring error.
    • If the DC voltage is significantly higher than the expected voltage, there is likely an open circuit.
Informational PurposesAn informational icon, calling your attention
Note
If the difference in DC voltage is an increment of the panel voltage, the string may be missing panels (voltage is too low) or have too many panels connected (voltage is too high). For instance, if the expected DC voltage for a system with 40V panels is 420V, but the test result is 380V, the string may be missing (1) PV panel.
Figure 1. Insulation Resistance Tester Displaying String Voltage (433V in this example)
Informational PurposesAn informational icon, calling your attention
Note
The diagram above illustrates example PV stringing configurations; the number of MCIs and where they are installed in the string varies by installation configuration.

Perform Insulation Resistance Test

Required Tools:
  • Insulation Resistance tester (Tesla recommends the Klein ET600 tester)
  • (2) extra MCIs

Testing Procedure:

  1. Temporarily connect the (2) extra MCIs to the string to test for ground faults:
    1. Create (4) jumpers, two for each MCI, by crimping MC4 connectors to short lengths of PV wire. Connect the jumpers to the extra MCIs.
    2. Connect the (2) extra MCIs to each end of the PV string.
  2. Set the voltage meter to 1kV test mode.
  3. Test positive to Ground :
    1. Connect the voltage meter positive lead to the string's positive conductor.
    2. Connect the voltage meter negative lead to the string's equipment grounding conductor (EGC).
    3. Insulate and protect the string's negative conductor, as it is live and is not being tested during this step.
    4. On the voltage meter, push the TEST button.
    5. Confirm the resistance value is greater than 1 MΩ. If the value is less than 1 MΩ, there is likely a damaged wire and/or ground fault in the system. Look for nicked or pinched wires, improper field-made connectors or improper crimps, or evidence of damaged modules that need to be replaced.
  4. Test negative to Ground :
    1. Connect the voltage meter negative lead to the string's negative conductor.
    2. Connect the voltage meter positive lead to the string's equipment grounding conductor (EGC).
    3. Insulate and protect the string's positive conductor, as it is live and is not being tested during this step.
    4. On the voltage meter, push the TEST button.
    5. Confirm the resistance value is greater than 1 MΩ. If the value is less than 1 MΩ, there is likely a damaged wire and/or ground fault in the system. Look for nicked or pinched wires, improper field-made connectors or improper crimps, or evidence of damaged modules that need to be replaced.
Informational PurposesAn informational icon, calling your attention
Note
The diagrams above illustrate example PV stringing configurations; the number of MCIs and where they are installed in the string varies by installation configuration.