Protective Earth Impedance Check
The protective earth (PE) connection is checked for sufficiently low impedance at least once per day.
The scheduled time for the PE impedance test is every morning before closing the inverter side AC relays.
Upon detected loss of PE or identification of a high impedance value Powerwall 3 does not connect to the grid until the fault is cleared manually or a repeated PE impedance test demonstrates a sufficiently low impedance.