Required Supplies
- Powerwall 3 Mounting bracket hardware (see Appendix A: Powerwall 3 Anchoring Details)
- mounting hardware
- Minimum
10 AWG, 600 V
rated, UV resistant, 90°C rated, copper (Cu) wire
- PV and AC wiring conductors must be made of solid wire, stranded wire or fine stranded wire. Forked wire terminals are recommended (required for fine stranded wire)
- AC conductor cross-section intake range: 10 AWG to 4 AWG (6 mm² to 25 mm²)
- PV conductor cross-section intake range: 10 AWG to 6 AWG (6 mm² to 16 mm²)
- Minimum
600 V rated communication cable with the following specifications (for
communication connection between Powerwall and the Backup Switch):
- 16 AWG or 18 AWG (according to wiring distance limits defined in Plan Cable Length Between Components)
- 4-conductor cable (two twisted pairs)
- Class 1 Circuit Listed
- Outdoor-rated
- Overall shield with drain
- RJ45 connectors for Ethernet wiring
- Conduit for Powerwall 3 AC and PV circuits:
- Powerwall 3 units with Tesla part number 1707000-11-L or 1707000-21-L: Metallic or non-metallic conduit
- All other Powerwall 3 units: Metallic conduit required
- Minimum
NEMA 4 (IPX5) or higher conduit hubs. Tesla recommends one of the following
options which meet this requirement:
- ¾ inch PVC-MC cable connector
- 1 inch PVC-MC cable connector
- ¾ inch Bridgeport 252-RTI2 connector
- 1 inch Bridgeport 252-RTI2 connector
- ¾ inch Rigid metal conduit (RMC) Myers hub with RMC conduit
- 1 inch Rigid metal conduit (RMC) Myers hub with RMC conduit
- ¾ inch RMC sealing locknut with RMC conduit
- 1 inch RMC sealing locknut with RMC conduit
- 1-¼ inch RMC sealing locknut with RMC conduit
NoteMinimum NEMA 4 (IPX5) fittings are required when installing outdoors. When Powerwall 3 is installed indoors and there is no risk of water ingress, indoor-rated fittings can be used. - ¾ inch, 1 inch, and 1-¼ inch conduit sealing washers
- Breaker for
the Powerwall 3 circuit: Select the
appropriate breaker size depending on the desired power / current output.
Power / Current Output (AC) Breaker (Overcurrent Protection) 11.5 kW / 48 A On-grid
15.4 kW / 64 A Off-grid80 A 11.5 kW / 48A (default) 60 A 10 kW / 41.67 A 60 A 7.68 kW / 32 A 40 A 5.8 kW / 24 A 30 A