Voltage Ride-Through

The inverter has five voltage and time setpoints for low voltage ride-through (LVRT), configurable to the following ranges (measured as Line-ground).

Table 1. Inverter LVRT Settings
Parameter Voltage Range Default Values for 240 V Time (sec)
LVRT Point 1 240V/208V 0.8 2
LVRT Point 2 240V/208V 0.6 1
LVRT Point 3 240V/208V 0.45 0.13
LVRT Point 4 240V/208V 0.45 0.13

The inverter has three high voltage ride-through setpoints, with one instantaneous trip voltage setting, configurable to the following ranges (measured as line to neutral):

Table 2. Inverter HVRT Settings
Parameter Voltage Range Default Values for 240 V Time (sec)
HVRT Point 1 240V/208V 1.1 1
HVRT Point 2 240V/208V 1.2 0.13
HVRT Point 3 240V/208V 1.2 0.13

Table 3. Trip Accuracy
Trip Setting Accuracy
Voltage +/- 2% of nominal voltage
Time Longer of +/- 100 mS or 1% of set point
Frequency +/- 0.05 Hz

Table 4. Voltage Ride-Through (L/HRVT) Ranges of Adjustability and Default Settings
Operating Region Voltage at Point of Interconnection (% of Nominal Voltage) Operating Mode Ride-Through Until (s) Default Maximum Trip Time (s) Range of Adjustability Voltage Trip Magnitude (% of Nominal Voltage) Range of Adjustability Clearing Time (s)
OV2 V>120 Cease to Energize N/A 0.16 N/A N/A
OV1 120≥V> 100 Mandatory Operation 0.92 1 110-120 1-13
CO 110≥V>100 Continuous Operation (Volt-Watt) N/A N/A N/A N/A
CO 100>V≥88 Continuous Operation N/A N/A N/A N/A
UV1 88>V≥70 Mandatory Operation 20 21 50-88 21-50
UV2 70>V≥50 Mandatory Operation 10-20 11-21 50-88 11-50
UV3 50>V Momentary Cessation N/A 2 N/A 0.5-21