Follow the table below for maximum distances between system components. Wire gauge must meet local codes and in some circumstances wire gauge requirements change based on distance. Refer to Appendix B: Wiring Reference for wire gauge requirements.

Distance to Measure Maximum Cable Length
Backup Switch to Powerwall+ unit(s)*

150 ft (45 m) for 16 AWG (1.5 mm2) wire
82 ft (25 m) for 18 AWG (0.8 mm2) wire

Neurio Energy Meter to Powerwall+ (RS485 wired connection) 164 ft (50 m)
Powerwall+ to Internet router (wired Ethernet connection) 328 ft (100 m)

*Total length of communications cable, including daisy-chained connections, through last Powerwall in chain

Informational PurposesAn informational icon, calling your attention
Note
As noted in Required Supplies, minimum 600 V rated 4-conductor (twisted pair optional) or double-insulated (with one twisted pair) shielded cable is required for the communication connection between Powerwall and the Backup Switch; see Required Supplies for custom cable requirements.
Warning IconA warning icon, calling your attention to a possibly risky situation
CAUTION
Failure to follow minimum cable size and length requirements may result in intermittent or unreliable operation of the Powerwall system. In systems that do not meet these minimum requirements, performance issues may arise even after successful device setup.

Maximum Neurio CT Extension

Neurio 200 A CTs (Remote Metering) Maximum Extension Length
Using Neurio CT extension harness (Tesla P/N 1622289-xx-y) Up to 15 ft (4.5 m)