Required Supplies

  • Mounting bracket hardware (see Appendix A: Powerwall+ Mounting Details)
  • Wiring methods (depending on local electrical requirements)
    • For installations where communication wiring must be protected, ½ inch LFNC Liquid Tight Flexible Non-metallic Conduit (LFNC) with NPT threaded fittings
    • For installation where communication wiring protection is not required, ½ inch NPT threaded cable glands
  • Minimum 600 V rated 4-conductor (twisted pair optional) or double-insulated (with one twisted pair) shielded cable (for communication connection between Powerwall and the Backup Switch)
    Informational PurposesAn informational icon, calling your attention
    Note
    If custom cable is used, it must meet the following specifications:
    • 16 AWG or 18 AWG (according to wiring distance limits defined in Plan Distance Between Components)
    • 4-conductor (twisted pair optional)
    • Class 1 Circuit Listed
    • Outdoor-rated
    • Overall shield with drain
  • Minimum 10 AWG, 600 V rated, UV resistant, 90°C rated, copper (Cu) wire
    • DC and AC wiring conductors must be made of solid wire, stranded wire or fine stranded wire. When using fine stranded wire, bootlace ferrules must be used.
    • Conductor cross-section intake range: 10 AWG to 6 AWG (6 mm² to 16 mm²)
  • Oxide-inhibiting electrical joint compound

Optional Supplies

  • Luggage lock (such as a Master Lock 120 series) for securing the solar assembly door shut