Connect Powerwall+ to the Backup Gateway

  1. Hardwired communications enter the Backup Gateway via the selected knockout. Run either LFNC or TCER cable using an appropriate ½ inch NPT fitting. Installer preference, Utility, and/or AHJ requirements will dictate whether LFNC or TCER cable should be used.
  2. Run the 4-conductor communication cable through the conduit or cable gland and pull it into the Backup Gateway.
  3. Wire the 4-conductor communication cable to the 4-pin connector plugged into the corresponding connector socket on the Backup Gateway:
    1. Strip the communication wire jacket about 3 inches and strip each conductor 0.4 inches (10 mm).
    2. Cut back the drain wire. The drain wire should be terminated at the Powerwall+ solar assembly ground terminal only.
    3. Insert a cabinet tip or electronics tip slotted screwdriver (up to 3 mm or 3/32 inch) to open each connector lever.
    4. Insert each conductor as far as possible into the terminal and then release the connector lever to close the connector.
  4. Plug the 4-pin connector into the 4-pin socket labeled "Powerwall". Tighten the screws on the connector.
    Informational PurposesAn informational icon, calling your attention
    Note
    Reference Backup Gateway 2 Communication Wiring for diagrams and wiring specifications.
  5. Wire the 4-conductor communication cable to the Powerwall+ solar assembly:
    1. Strip the communication wire jacket about 3 inches and strip each conductor 0.4 inches (10 mm).
    2. Insert a cabinet tip or electronics tip slotted screwdriver (up to 3 mm or 3/32 inch) into each actuation shaft to open the terminal.
    3. Insert each conductor as far as possible into the terminal and remove the screwdriver from the actuation shaft to close the terminal.
      Informational PurposesAn informational icon, calling your attention
      Note
      Reference Backup Gateway 2 Communication Wiring for the correct wire order in the Backup Gateway connector.
    4. (Optional) If the drain wire is present, insert it in the solar assembly ground terminal.
    Informational PurposesAn informational icon, calling your attention
    Note
    See Plan Distance Between Components for the maximum distance between components.