General Warnings and Information
ATTENTION: Read this entire document before installing or using Powerwall+. Failure to do so or to follow any of the instructions or warnings in this document can result in electrical shock, serious injury, or death, or can damage Powerwall+, potentially rendering it inoperable.
Note
On detection of abnormal condition for
voltage or frequency conditions or in response to a detected unintentional island, the
Tesla Powerwall+ system disconnects from the grid to
prevent backfeed.
Important Safety Instructions
Symbols Used
General Information
Warning
Powerwall+ installation must be carried out only by a competent electrician who is certified
by Tesla and who has been trained in dealing with low voltage electricity.
Warning
Electric shock hazard. The DC conductors of this PV system are
normally ungrounded but will become intermittently grounded without indication when
the inverter measures the PV array isolation. Energy stored in capacitor. Do not
remove cover until 5 minutes after disconnecting the equipment. Power fed from more
than one source. Disconnect all sources of supply before servicing.
Warning
Do not touch
non-insulated cable ends.
Warning
Do not touch the DC
conductors when energized.
Warning
Do not touch any
live components of the inverter.
Warning
If an error occurs,
have it rectified by qualified persons only.
Warning
Before beginning the
wiring portion of the installation, ensure that Powerwall+ is switched off, and lock out any associated circuit breakers and disconnect
switches (if applicable for the installation).
Warning
Prior to performing
any work on Powerwall+, disconnect it from all voltage sources as described in this document.
Warning
Connect and ground
the PV modules, array frame, and non-current carrying electrically conductive
components so that there is continuous conduction. Observe the applicable local
regulations.
Warning
This Photovoltaic
Rapid Shutdown Equipment (PVRSS) does not perform all of the functions of a complete
Photovoltaic Rapid Shutdown Equipment (PVRSS). This PVRSS must be installed with
other equipment to form a complete PVRSS that meets the requirements of NEC (NFPA
70) section 690.12 for controlled conductors outside the array. Other equipment
installed in or on this PV system may adversely affect the operation of the PVRSS.
It is the responsibility of the installer to ensure that the completed PV system
meets the Rapid Shutdown functional requirements. This equipment must be installed
according to the manufacturer’s installation instructions.
Warning
Risk of electric
shock and fire. Use only with PV modules with a maximum system voltage of rating of
600 V or higher.
Warning
A battery can present a risk of electrical shock, fire, or
explosion from vented gases. Observe proper precautions.
Warning
Powerwall+ is heavy. Use of lift equipment is recommended.
Warning
Use Powerwall+ only as directed.
Warning
Do not use Powerwall+ if it is defective, appears cracked, broken, or otherwise damaged, or fails to
operate.
Warning
Do not attempt to
open, disassemble, repair, tamper with, or modify Powerwall+. Powerwall+ and its components are not user serviceable. Batteries in Powerwall+ are not replaceable. Contact Tesla Support for guidance on repairs.
Warning
To protect Powerwall+ and its components from damage when transporting, handle with care. Do not
impact, pull, drag, or step on Powerwall+. Do not subject Powerwall+ to any strong force. To help prevent damage, leave Powerwall+ in its shipping packaging until it is ready to be installed.
Warning
Do not insert
foreign objects into any part of Powerwall+.
Warning
Do not expose Powerwall+ or its components to direct flame.
Warning
Do not install Powerwall+ within 24 inches (610 mm) of
heating vents or radiators. Powerwall can be installed in a mechanical room with
HVAC equipment.
Warning
Do not immerse Powerwall+ or its components in water or other fluids.
Warning
Install Powerwall+ in a location that prevents damage from flooding.
Warning
Risk of electric
shock. Do not remove cover, there are no user serviceable parts inside. Refer
servicing to qualified personnel.
CAUTION
Where supplied by a photovoltaic (PV) system, the Powerwall shall
not be installed within the PV array boundary as defined in NEC Article 690.
CAUTION
Both AC and DC voltage sources are terminated inside this
equipment. Each circuit must be individually disconnected before servicing.
CAUTION
When the PV array is exposed to light, it supplies a DC voltage to
this equipment.
CAUTION
Powerwall+ is not designed nor warrantied for non-stationary applications.
CAUTION
Do not expose Powerwall+ to ambient temperatures above
60°C (140°F) or below -30°C (-22°F).
CAUTION
Operating or storing
Powerwall+ in temperatures outside its
specified range might cause damage to Powerwall+.
CAUTION
Equipment shall be
installed and operated in an environment within the ratings and limitations of the
equipment as published in these installation instructions.
CAUTION
Do not use solvents
to clean Powerwall+, or expose Powerwall+ to flammable or harsh chemicals or vapors.
CAUTION
Do not use fluids, parts, or accessories other than those specified
in this manual, including use of non-genuine Tesla parts or accessories, or parts or
accessories not purchased directly from Tesla or a Tesla-certified party.
CAUTION
Do not place Powerwall+ in a storage condition for more than one (1) month, or permit the electrical feed
on the Powerwall+ to be severed for more than one (1) month, without placing Powerwall+ into a storage condition in accordance with Tesla’s storage
specifications.
CAUTION
Do not paint any
part of Powerwall+, including any internal or external components such as the exterior shell or
casing.
CAUTION
When installing Powerwall+ in a garage or near vehicles, keep it out of the driving path. If possible,
install Powerwall+ on a side wall and/or above the height of vehicle bumpers.
CAUTION
Ensure that no water
sources are above or near Powerwall+, including downspouts, sprinklers, or faucets.
CAUTION
Ensure that snow
does not accumulate around Powerwall+.