Performance Specifications
| AC Voltage
(Nominal) |
120/240
V |
| Feed-In Type |
Split Phase |
| Grid Frequency |
60 Hz |
| Current
Rating |
200 A |
| Maximum Input Short Circuit Current |
10 kA1 |
| Overcurrent
Protection Device |
100-200A; Service Entrance Rated1 |
| Overvoltage
Category |
Category IV |
| Internal
Primary AC Meter |
+/– 0.2% |
| Internal
Auxiliary AC Meter |
+/– 2% |
1 When
protected by Class J fuses, Backup Gateway 2 is suitable for use in circuits capable
of delivering not more than 22 kA symmetrical amperes.
Mechanical Specifications
| Dimensions |
26 x 16 x 6 inches (660 x 411 x 149 mm) |
| Weight |
45 lb (20.4 kg) |
| Mounting |
Wall mount, Semi-flush mount |
Environmental Specifications
| Operating Temperature |
–4°F to 122°F (–20°C to 50°C) |
| Operating
Humidity (RH) |
Up to 100%, condensing |
| Maximum
Elevation |
9843 ft (3000 m) |
| Environment |
Indoor and outdoor rated |
| Enclosure
Type |
NEMA 3R |