Other Function Parameters
Description | Value |
---|---|
Output current rating (Aac) | 32/16 |
Minimum normal ramp-up rate (%Irated / sec) | 1 |
Maximum normal ramp-up rate (%Irated / sec) | 100 |
Output current range of function (%Irated) | 0% to 100% |
Ramp rate accuracy (%Irated / sec) | 2% |
Description | Value |
---|---|
Output current rating (Aac) | 32/16 |
Minimum normal ramp-up rate (%Irated / sec) | 0.1 |
Maximum normal ramp-up rate (%Irated / sec) | 100 |
Output current range of function (%Irated) | 0% to 100% |
Ramp rate accuracy (%Irated / sec) | 2% |
Description | Value |
---|---|
Apparent power rating (VA) | 7600/3800 |
Output power rating (W) | 7600/3800 |
DC Input voltage range with SPF enabled (Vdc) | 185-515 |
Nominal AC voltage (Vac) | 240/208 |
AC voltage range with SPF enabled (Vac) | (211.2-264), (183.04-228.8) |
Active power range of function (W) | 0-7600,0-3800 |
Manufacturer's stated Power Factor accuracy | ±0.01 |
Power factor settling time (sec) | 0.04 |
Minimum Inductive (underexcited) Power Factor | 0.9 |
Minimum Capacitive (overexcited) Power Factor | 0.9 |
Description | Value | ||||
---|---|---|---|---|---|
Apparent power rating (VA) | 5769 | 5000 | 2884 | 2500 | |
Reactive power rating (VAR) (Reactive Power Priority) | 5769 | 5000 | 2884 | 2500 | |
Output power rating (W) | 7600 | 6600 | 3800 | 3300 | |
EUT Input voltage range with Q(V) function enabled (Vdc) | N/A | ||||
Nominal AC EPS voltage (V) | 240 | 208 | 240 | 208 | |
AC EPS voltage range with function enabled (Vac) | 196.8 – 283.2 | 170.3-245.4 | 196.8 – 283.2 | 170.3-245.4 | |
Reactive Power Accuracy (% or Var) | ±2.5% | ||||
Ramp Rate range (VAr/sec) | 5769 - 32.2 | 5000-27.90 | 2884-16 | 2500-14 | |
Max rated reactive Power (capacitive, overexcited) (VAr) - | 5769 | 5000 | 2884 | 2500 | |
Max rated reactive Power (inductive, underexcited) (VAr) | 5769 | 5000 | 2884 | 2500 | |
Maximum slope (VAr/V) | 1200 | ||||
Deadband Range (Vac) | 0 - 48 | ||||
Settling Time (sec) | 1-90 | ||||
Max rated reactive Power (capacitive, overexcited) (VAr) (Active Power Priority) | 5769 | 5000 | 2884 | 2500 | |
Max rated reactive Power (inductive, underexcited) (VAr) (Active Power Priority) | 5769 | 5000 | 2884 | 2500 |
Description | Value | ||||
---|---|---|---|---|---|
Output power rating (W) | 7600 | 6600 | 3800 | 3300 | |
Nominal AC EPS voltage (V) | 240 | 208 | 240 | 208 | |
AC frequency range with function enabled (Hz) | 60.017 - 65 | ||||
Manufacturer's stated frequency measurement accuracy | 0.05 | ||||
Manufacturer's state power accuracy (%) | ±5 | ||||
Settling Time (sec) | 0.5 to 3 | ||||
Adjustment range of the start of frequency droop (Hz) | 60.017 - 65 | ||||
Rate of return (%Prated/sec) | 1% - 100% | ||||
Delay before return to full power (sec) | 1 – 600 | ||||
Use of hysteresis | Yes |
Description | Value | ||||
---|---|---|---|---|---|
Output power rating (W) | 7600 | 6600 | 3800 | 3300 | |
AC voltage range with function enabled | 247.2 – 288 | 214.24 – 249.6 | 247.2 – 288 | 214.24 – 249.6 | |
Nominal AC voltage (Vac) | 240 | ||||
Manufacturer's stated AC voltage accuracy (Vac) | ±2% | ||||
Manufacturer's stated output power accuracy (%) | ±3% | ||||
Manufacturer's stated time accuracy (sec) | 0.1sec |
The above values are used to comply with all applicable source requirements documents (UL 1741 Supplement SA – Grid Support Utility Interactive Inverters and Converters, Sept. 7, 2016 with the source requirements document (SRD) v1.1–Hawaii Rule No. 14H Interconnection of Distributed Generating Facilities with the Distribution System; Electric Rule No.21-2015 Generating Facility Interconnections; PRC-024-2 Generator Frequency and Voltage Protective Relay Settings; Inverter Source Requirement Document of ISO New England) and any related features required therein.