Powerwall+ Space Requirements
Minimum lateral wall space | 38 in (960 mm) |
Minimum clearance from left side (air intake)1 | 2 in (50 mm) |
Minimum clearance from right side (air exhaust) | 6 in (150 mm) |
Minimum clearance above a single Powerwall+ | 2 in (50 mm) |
Minimum clearance above side-by-side Powerwall+ units | 12 in (300 mm) |
Minimum clearance between side-by-side Powerwall+ units | 10 in (250 mm) |
Maximum height above ground | 39.5 in (1 m) to bottom of unit |
Maximum slope |
+/– 2° side-to-side |
1Ensure there is sufficient working space to connect Powerwall+ wiring. Tesla recommends at least 200 mm of working space to the left of the unit.
Note
Powerwall+ meets the unit level performance criteria
of UL 9540A, allowing Powerwall+ to be installed side-by-side as long as
the clearance requirements defined in this manual are followed to allow for air flow around
the units.
Note
Powerwall+ has a pump and fan that produce a gentle hum during operation, comparable to a typical
refrigerator. The noise level depends on the ambient temperature and the power level of
operation. Consider these noise levels when choosing where to install Powerwall+.