Concrete Pad Details for Ground-mounting Powerwall+ on Pre-Cast Concrete Pad an Existing Structural Wall
A7
In this mounting configuration, a concrete pad is placed at the base of the existing wall capable of supporting Powerwall+. Powerwall+ is mounted to the wall, allowing it to be vertically supported by the concrete pad and laterally supported by the existing wall.
Note
Refer to Powerwall+ Anchoring Details for more
information.
Concrete Pad Sizes
Number of Units | Pad Width | Pad Length |
---|---|---|
1 Powerwall+ | 16 in (406 mm) | 34 in (864 mm) |
1 Powerwall+ and 1 Powerwall | 16 in (406 mm) | 34 in (864 mm) |
Concrete Pad Requirements
- Within the perimeter of the pad, excavate and remove all loose and organic material, compacting soil to a level surface. Embed the concrete in the soil per detail (below). Should AHJs require further embedment of footing, contractors shall consult a third party structural designer or other qualified person acceptable to the AHJ to abide by the requirements set by the AHJ.