Configuring Conductor Export Limits
Overview
Backup Gateway 2 can be configured to limit Powerwall discharge power. When Conductor Export Limits are programmed, the Powerwall discharge power is dynamically adjusted based on the amperage measured by designated current transformers (CTs) and the programmed Conductor Limit amperage threshold.
Set Conductor Export Limits
Install CTs
- Conductor CTs must be installed on conductors that are:
- Between the grid connection and the Powerwalls.
- At a location where the Powerwalls have control over current.
- CTs should be oriented such that the label faces toward the grid.
Complete Commissioning
- In Tesla One, assign the
correct CTs to Conductor.NoteCTs can only be assigned one designation, meaning a CT cannot be both a Site and a Conductor CT.NoteSee the Powerwall Device Setup Guide for instructions to connect to the TEG Wi-Fi network in Tesla One.
- Enter the amperage for the Conductor Limit on the Settings page.
At the conclusion of the commissioning process, a summary of the settings will be displayed.