Step 4: Join the Units
- Orient the Powerwall about 1 in (2 cm) in front of the Powerwall+, with its back cable entry port facing the hole you drilled in the Powerwall+.
-
(Concealed wiring installations
only) Do the following to bridge the gap between the Powerwall+ and Powerwall wiring compartments:
- (All installations) Locate a side clip, making sure the flange (with magnet) is positioned at the top and that the cams are rotated vertically in relation to the clip.
- Slide the side clip into the gap between the Powerwall+ and Powerwall so that its flanges engage the side hem of each enclosure.
- Press the clip until it is flush with the sides of the units.
-
Using the provided 6 mm Allen hex wrench, do the following:
-
Repeat steps 3-6 to install a
side clip on the other side of the units.
NoteIf necessary, use a small rubber mallet or a hammer and wood block to gently tap the side clips so that they are fully seated in the hem of the unit.
- Position the top cover across the gap between Powerwall+ and Powerwall so that its flanges engage the tops of each side clip. The cover is held in place by the magnets on the tops of the side clips.
- (Concealed wiring installations only) Tighten the insulation bushing on each side of the conduit nipple to secure the bridge between the two wiring compartments.
- Use shims to ensure the Powerwall is level.