Turn the Powerwall 3 Enable switch OFF to de-energize
the system before terminating any conductors inside Powerwall 3. Confirm lack of voltage at the AC
and PV terminals before proceeding.
Symptoms
On the landing page, solar production is lower than expected. On the Powerwall 3 Device page, the correct number
of strings is displayed (the connected strings appear as green), but the solar
production value for one or more strings is lower than expected.
Steps to Troubleshoot
Note
Powerwall 3 solar is automatically enabled
when the system is started. There is no Enable button for solar.
Once the system is started, wait up to 30 minutes for Powerwall 3 to start production. It may
take time for production to start, particularly if it is a cloudy day; this is
likely the issue if voltage is as expected (per the planset) but amperage is
low.
If the voltage displayed
in Tesla One is lower than expected:
See Determine True String VOC for
instructions to conduct an open air voltage test to see string VOC.
Note
Alternatively, select
Stop
System then Start System,
then navigate to the Powerwall 3 device page. It
is possible to see VOC during the PV Isolation
Self-Test.It is important to note that this method will not identify
instances of reversed string polarity (see Confirm String Continuity
for more details. The open air voltage test DOES identify reversed
string polarity.
Confirm each string
displays the expected voltage (VOC) as displayed on the planset.Figure 1. Comparing Powerwall 3 String
Voltage with Expected Voltage on Planset
Note
If strings do
NOT display the expected voltage, review the VOC of all strings
before proceeding. Consider the following scenario:
String A has
an expected voltage of 350 VDC but displays a VOC of 410
VDC
String B has
an expected voltage of 410 VDC but displays a VOC of 350
VDC
In this scenario String A was mislabeled as String B and vice
versa, and there is not production issue.
Note
If a planset
with expected VOCs is not available, each string's expected VOC can
be calculated by multiplying the panel VOC (found on the panel
datasheet) by the number of modules in the string. For instance, a
string of 5 modules that have a module VOC of 45.27 would have an
expected string VOC of 226.35 V
If the VOC is significantly lower
than the expected VOC on the planset, confirm the system stringing is correct
according to the planset:
Confirm all panels in the
string are connected. Missing panels would result in a lower VOC than
expected.
Confirm all modules have
been connected properly (positive to negative). Any module with reverse
polarity (positive connected to positive and negative connected to
negative) subtracts from the positive voltage of the string. For
instance, if there are 5 modules connected with correct polarity, and 2
modules connected with reverse polarity, the string VOC will reflect
only 3 modules.
Confirm that any combined
(paralleled) strings have been wired according to the planset, and that
they have been combined correctly (both positives combined and both
negatives combined, no positive combined with negative). Not paralleling
strings as outlined will result in the system under-producing.
Confirm that MPPT jumpers
have been installed according to the planset.
Note
Jumpers are required
when Imp > 13A. As displayed in the examples below, paralleled
strings with a combined Imp < 13 A do not require an MPPT
jumper.
Figure 2. Example 1: Powerwall 3 with Solar
PanelsFigure 3. Example 2: Powerwall 3 with Solar
Roof
If all wiring has been
performed correctly, look for evidence of damage that may be causing the
string to under perform:
Inspect where the
wires exit conduit, as nicked wires may occur here
Check for wires
pinched by mounting hardware
If the VOC is correct (matches
the expected VOC on the planset), confirm Powerwall 3 is not the issue by testing
the string in another MPPT:
Select Stop System on
the landing page in Tesla One, then turn Powerwall 3 OFF.
Warning
Confirm Powerwall 3 is de-energized
before disconnecting or connecting any PV strings.
Disconnect a functional
string (displays the correct voltage and amperage when the system is
running) from its MPPT (consider this a functional MPPT).
Disconnect the
problematic string from its MPPT, then connect the problematic string to
the functional MPPT.
Turn the system back ON
and Start
System.
If the problematic string
now displays the correct voltage and amperage (while plugged in to the
functional MPPT), contact Tesla Support for additional troubleshooting
support.
Note
Turn
Powerwall 3 OFF again and
move the string back to its original (presumed faulty) MPPT to
confirm that MPPT still does not function. If, upon moving back to
the original MPPT, the string displays the correct voltage, the
issue is resolved. No additional action is required.
If the string is still displaying
low voltage while plugged in to the functional MPPT, the issue is not Powerwall 3. The system may have a
faulty MCI; perform the troubleshooting steps in MCI Diode Test and Resistance Test (MCI Health Tests) to identify the faulty
MCI(s).
If the amperage displayed
in Tesla One is lower than expected and
none of the previous troubleshooting steps have resolved the issue:
Look for greater shade
than anticipated (may be caused by snow or leaves). Heavy shade would
result in a lower current than expected.
Perform an irradiance
test for each string on the roof:
Place an
irradiance meter on the roof, facing the same direction as the
modules in the string.
Calculate the expected amperage for the string by multiplying
the irradiance value by the IMP of the PV module,
then dividing that value by 1000; for instance:
Irradiance reading = 363 W/m2
PV module IMP = 9.12 A (found on module
datasheet)
If the irradiance
values are lower than 100 W/m2,
light levels are likely too low for accurate testing (meaning
low amperage would be expected in the Tesla One
interface).
If the amperage
displayed in Tesla One is
significantly lower than the calculated expected amperage,
measure each string's amperage individually. Confirm each string
is producing an amperage value; if one is not, perform the
troubleshooting steps in MCI Diode Test and Resistance Test (MCI Health Tests) to
inspect the MCIs in that string.
If a string is
producing unexpectedly low amperage, inspect that string for
wiring errors. For combined (paralleled) strings, confirm each
individual string is producing amperage, and confirm they have
been combined correctly and are connected properly.