Powerwall 3 Discharge is Fluctuating
Powerwall 3 is displaying rapid spikes of charging and discharging
Steps to Troubleshoot
- Ensure the CT has been placed in the correct location and is measuring the
correct conductor(s):
- Verify the CT is clamped properly
around the intended conductor(s). WarningBefore installing, disconnecting, and/or adjusting CTs, ensure the circuits being measured are not energized and the system is completely powered down. Failure to de-energize the system may compromise operator and equipment safety.
- Verify the CT is not capturing any
other conductor(s).NoteIf a site has multiple inverter outputs and their conductors are being grouped, ensure every conductor is captured.
- Verify the CT is clamped properly
around the intended conductor(s).