Arc Fault Lockout
Symptoms
If a Powerwall 3 experiences five Arc Fault alerts within 24 hours, an Arc Fault lockout will occur. A comprehensive inspection must be performed to identify and remediate the issue(s) causing the alert. The following system components must be inspected:
- System stringing
- Powerwall 3 wiring
- Solar junction boxes
- DC Connectors
- MCIs
Tesla Installers: Open a Maintenance-Arc Fault Field Visit Tesla One Form
Note
This form is only available for Tesla installers; Certified Installers can
skip this step.
- Open the job in the Tesla One app and add a new Maintenance-Arc Fault Field Visit form to the job.
- Complete the form as you complete the following troubleshooting steps, uploading screenshots and/or photos as potential causes are ruled out. If Install Support is required, they will use these screenshots to verify the steps that have been ruled out and can be skipped during the call.
Note
The Maintenance-Arc Fault Field Visit form acts as a checklist for the
troubleshooting procedure. Follow the steps in the form to complete the
troubleshooting process with no additional instructions required.
Inspect the Powerwall 3
- On the Tesla One landing page, select Stop System.
- If a System Shutdown Switch is present, push it to initiate Rapid Shutdown.
- If Powerwall 3, turn the Powerwall Enable switch OFF, then turn the Powerwall breaker OFF.
- Perform Lockout/Tagout to secure
the system against being re-energized.WarningConfirm Powerwall 3 is de-energized before investigating any wiring.
- Perform a tug test on each DC string connected to the Powerwall 3 terminal block. Ensure they are landed securely.
- For paralleled strings, ensure
the MPPT jumpers are properly installed:
- Valid configuration for Powerwall 3: jumper from 1 to 2 or 5 to 6
- Take photos of the Powerwall 3 serial number via the
Device Setup interface vs. the serial number on the actual sticker in the
enclosure to confirm they match.
- If the serial numbers do not match, look for other units to confirm you are connected to the correct network and are configuring the correct unit.
- If the serial numbers do not match and there are no other units, or if you have confirmed you are connected to the correct unit, contact Install Support to fix the discrepancy.
- Check all wiring to ensure there are no nicks or cuts in the insulation that might create a short with the ground.
- Take a pullback photo of the Powerwall 3.
Inspect Wiring on the Roof
- Verify all strings are
connected as outlined in the planset and string diagram.
- See Powerwall 3 is Under Producing for instructions to check wiring against the planset.
- See Determine True String VOC for instructions to measure each string's
voltage, then compare that voltage with the planset to confirm that
each string is labeled correctly and landed at the correct terminal.
NoteFor instance, if MPPT 4 has been identified as the faulty string, but String 3 is landed there instead of String 4, the installer could spend time troubleshooting a string with no faults. In this case, comparing each string's voltage with the planset would identify this issue and the installer could correct it before moving to the roof to troubleshoot String 4.
- Perform a tug test on all
vulnerable connection points on the roof:
- Wiring in junction boxes (look for frayed wires, conductors pulled too tightly). Ensure jumpers in J-boxes are secure along with wires.
- Ensure all MC4 connectors on the roof are secure and not loose. Check for any signs of thermal damage (deformation, bulging, glossy finish, etc.)
- Confirm all components have been installed to the standards of Tesla AND the original manufacturer (if applicable). Modifications made to wiring terminals or terminal connections can cause unexpected failures.
- See MCI Diode Test and Resistance Test (MCI Health Tests) to determine if a faulty MCI is causing the Arc Fault.
After identifying and addressing the potential cause of the Arc Fault, retry the self-test by selecting Stop System then Start System. All self-tests should pass to confirm the issue was resolved.