Powerwall 3 is Discharging at Full Power
Powerwall 3 is discharging at its maximum discharge, and the site reading increases as Powerwall 3 discharges
Steps to Troubleshoot
- If using external Site CTs:
- Confirm the CTs are
facing the correct way:
- Locate the CT(s) used to measure the source that is displaying incorrect power flow readings.
- Verify the CT(s) are oriented such
that the label is facing toward the source (away from the breaker).
- Solar Current Transformer: Label toward the inverter
- Site Current Transformer:
Label toward the Grid
Figure 1. Tesla 200 A CT (for Tesla Remote Energy Meter) Orientation in Relation to Power Flow ➀ Figure 2. Tesla 100 A CT (for Backup Gateway 2) Orientation in Relation to Power Flow
- Confirm the CTs are
measuring the correct phase:
- Locate the CT on the Meter page in the Device Setup interface in Tesla One.
- Determine which phase the CT should
be measuring.
- Backup Gateway 2 with
Tesla 100 A CTs:
CT1 Line 1 CT2 Line 2 CT3 Defaults to Line 1 but can be configured as Line 2 during device setup in Tesla One - Tesla Remote
Meter with Tesla 200 A
CTs:
CT1 Line 1 CT2 Line 2 CT3 Line 2 CT4 N/A (CT4 functionality will be available at a later date)
- Backup Gateway 2 with
Tesla 100 A CTs:
- Verify the CT is measuring the correct phase.
- Confirm the CTs are
facing the correct way:
- For systems with Backup Gateway
2 or Gateway 3, verify the supply
conductors feeding the Gateway are connected to the Supply terminals:
- Verify any backup conductors are connected to the
Backup terminals (or the internal panelboard if it is connected to the Backup
terminals):