Negative Site Reading
On the landing page, the site value is negative. An alert will appear on the landing page
Steps to Troubleshoot
- Confirm the CTs are facing
the correct way:
- Locate the CT(s) used to measure the source that is displaying incorrect power flow readings.
- Verify the CT(s) are oriented such
that the label is facing toward the source (away from the breaker).
- Solar Current Transformer: Label toward the Inverter
- Site Current Transformer: Label toward the Grid
- Confirm the CTs are measuring
the correct phase:
- Locate the CT on the Meter page in Tesla One.
- Determine which phase the CT should
be measuring.NoteIf using Gateway CTs, the ports are CT 1 (Line 1), CT2, (Line 2), CT 3 (defaults to Line 1 but can be configured as Line 2 in Tesla One).
- Verify the CT is measuring the
correct phase. NoteIn the examples above, the CT is monitoring a solar inverter conductor, which is why only (1) CT is required.
Note
The site value can be negative
if power is flowing to the grid.