Backup Switch with Tesla P/N
1624171-xx-L or greater is
required for Powershare home backup installations.
Performance Specifications
Continuous
Load Rating
200A, 120/240V Split phase
Short Circuit Current Rating
22 kA with breaker1
Communication
CAN
AC
Meter
+/- 0.5%
1The breaker
size must be equal to or greater than the available fault current and can be
installed either upstream or downstream of the Backup Switch. This Backup Switch is
rated for use on a circuit delivering not more than 10,000 RMS symmetrical amperes,
300 V maximum. When used in conjunction with a circuit breaker rated not more than
200 A, the Backup Switch is rated for use on a circuit capable of delivering not
more than 22,000 RMS symmetrical amperes, 300V maximum, not in excess of circuit breaker
interrupting rating. Watthour meter not included in short circuit current
rating.
Compliance Information
Safety Standards
USA: UL 414, UL 414 SB, UL 2735, UL 916, CA Prop
65
Emissions
FCC Part 15, Class B, ICES 003
Mechanical Specifications
Dimensions
6.9 x 8.1 x 2.9 inches (176 x 205 x 74
mm)
Weight
2.8 lb (1.27 kg)
Meter and
Socket Compatibility
ANSI Type 2S, ringless or ring type
External Service Interface
Contactor manual override2,
Reset button
Conduit
Compatibility
½-inch NPT
2Manually
overrides the contactor position during a service event.