Plan the Electrical Service Connection to Gateway
The Powershare Gateway is service entrance rated. When installed at the service entrance, appropriate overcurrent protection must be installed in the Powershare Gateway. The Powershare Gateway can accommodate a main circuit breaker between 100 and 200 A. Breaker sizing and installation must comply with the local code requirements.
Note
Powershare
Gateway is not to be used as service entrance equipment in Canada.