Powershare Gateway Wiring

Component Wire Color Wire Gauge 1 Torque
A Supply Terminals Black, Red 6 AWG – 250 kcmil 275 in-lb, 23 ft-lb
B Backup Terminals Black, Red (1x) #4 AWG - 250 kcmil, or

(2x) #4 AWG - 4/0 stranded2

250 in-lb, 21 ft-lb
C Main Neutral Terminals White (1x) #4 AWG - 250 kcmil, or

(2x) #4 AWG - 4/0 stranded2,3

250 in-lb, 21 ft-lb
D Load / Generation Neutral Terminals White See table in Gateway Neutral Bar and Ground Bars
E Backup Terminals on Internal Panelboard Black, Red 6 AWG – 250 kcmil 275 in-lb, 23 ft-lb
F Main Ground Terminals Green or Bare 6 AWG – 2/0 120 in-lb, 10 ft-lb
G Load/Generation Ground Terminals Green or Bare See table in Gateway Neutral Bar and Ground Bars

1 Use copper or aluminum conductors rated to a minimum of 75°C.

2 Conductors must be the same size and material when terminating two conductors under these terminals.

3Double lugging is allowed only when conductors are paralleled (part of the same circuit) to increase ampacity for a single circuit.

Warning IconA warning icon, calling your attention to a possibly risky situation
CAUTION
Do not modify the factory lug configuration.